Table 3: External control inputs

Audible alarm reset

NO contact circuit

Alarm acknowledge

NO contact circuit

Alarm channel reset

NO contact circuit

Remote testing

NO contact circuit

Control of unit into LOCAL mode

NO contact circuit

Control of unit into REMOTE mode

NO contact circuit

Clock synchronization

NO contact circuit, pulse length
> 100 ms, 48 V dc, 4 mA

Table 4: Data communication

Transmission mode

Fibre-optic serial bus

Coding

ASCII

Data transfer, selectable

4800 or 9600 Bd

Electrical/optical bus 
connection module, 
powered from the host 
unit

for plastic core cables

SPA-ZC 21BB/S

for glass fibre cables

SPA-ZC 21MM/S

Electrical/optical bus 
connection module, 
powered from the host 
unit or from an external 
power source

for plastic core cables

SPA-ZC 17BB/S

for glass fibre cables

SPA-ZC 17MM/S

Table 5: Auxiliary supply modules

Type of module

SPGU 240A1

rated voltages U

n

110/120/230/240 V ac
110/125/220 V dc

operative range

80…265 V ac/dc

SPGU 48B2

rated voltages U

n

24/48/60 V ac

operative range

18…80 V dc

Power consumption under quiescent/operation 
conditions

~20 W/~30 W

Table 6: Tests and standards

Test voltages

Between channel and control inputs and annunciator case, supply inputs and 
relay outputs
Dielectric test voltage (IEC 60255-5)

500 V, 50 Hz, 1 min

Impulse test voltage (IEC 60255-5)

1 kV, 1.2/50 

µ

s, 0.5 J

HF test voltage (IEC 60255-5)

1 kV, 1 MHz

Test voltages

Between supply inputs and case, relay outputs and case, supply inputs and 
relay outputs between themselves
Dielectric test voltage (IEC 60255-5)

2 kV, 50 Hz, 1 min

Impulse test voltage (IEC 60255-5)

5 kV, 1.2/50 

µ

s, 0.5 J

HF test voltage (IEC 60255-5)

2.5 kV, 1 MHz

Environmental conditions

Ambient service temperature range 
without matrix display

-10…+55

°

C

Ambient service temperature range, 
including matrix display

-10…+45

°

C

Long term damp heat withstand 

 

(IEC 60068-2-3)

<95%, +40

°

C, 56 d/a

Ambient transport and storage 
temperature range

-20…+55

°

C

Degree of protection by enclosure when 
panel-mounted

IP 54

Weight of annunciator unit

~4.5 kg

Analog Annunciator Unit

Product Guide

SACO 16 A3

1MRS750405-MBG

6

Summary of Contents for SACO 16 A3

Page 1: ...Analog Annunciator Unit Product Guide SACO 16 A3...

Page 2: ......

Page 3: ...rameter ization of the relay for reading measured and recorded values events etc and for storing readings Member of the SPACOM product family and ABB s Distribution Automation system CE marking accord...

Page 4: ...panel or via the serial interface When a measured signal exceeds or falls below the set start value of the channel a visual indication is obtained on the alarm panel At the same time the acoustic ala...

Page 5: ...r signal limit values Transducer circuit earth fault supervision Integrated with a sensitivity of 5 10 k Transducer oscillation supervision Selectable 1 255 events s Can even be set out of function Re...

Page 6: ...nge 80 265 V ac dc SPGU 48B2 rated voltages Un 24 48 60 V ac operative range 18 80 V dc Power consumption under quiescent operation conditions 20 W 30 W Table 6 Tests and standards Test voltages Betwe...

Page 7: ...gue 48 V Audible alarm Internal supervision Man machine interface SPA bus connection Auxiliary supply 1 st 2 nd Transducer supply and cable shield connection 16 transducer connections Remote ackn rese...

Page 8: ...14 154 a b a b SFM16D3 Fig 8 Semi flush mounting relay case dimensions in mm Mounting in 19 inch cabinets and frames An ancillary mounting plate height 4U 177 mm is recommended to be used when the aci...

Page 9: ...equirements Table 11 Order numbers Analog annunciator unit SACO 16A3 RS 812 016 AA BA Analog annunciator unit SACO 16A3R without a dot matrix display on the front panel RS 812 015 AA BA The last two l...

Page 10: ......

Page 11: ......

Page 12: ...ABB Oy Distribution Automation P O Box 699 FI 65101 Vaasa FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 www abb com substationautomation...

Reviews: