36
Remote information
to and from the
alarm annunciator
The following parameters can be read out or
written down to the annunciator unit from a
higher level device.
Code
Factory
Value and function
setting
Module related parameters
V205
-
Program version
S1
0
Reflash output 1 sequence
0 = FCFR
1 = AACR
2 = ISR
3 = FCFR + ISR
4 = FCFR + AACR
S2
0
Reflash output 1 sequence
S17
3
Alarm sequences
0 = ISA A
1 = ISA A-1
2 = ISA M-1
3 = ISA R-1
4 = DIN 19235
S18
0
Specification of active channels to be printed out as a result when
parameter A is read out
0 = both alarm and status channels are printed out
1 = only alarm channels are printed out
2 = no out printing
S19
0
Pumping supervision output relay
00 = not connected
01 = output relay 1
02 = output relay 2
S33
0
Control of the output relay 1 over the SPA bus
0 = not active
1 = changing of state (on/off)
2 = pulse activation
S34
0
Control of the output relay 2 over the SPA bus
S49
0
Pulse length of output relay 1
0,3...25,5 = pulse length in seconds
S50
0
Pulse length of output relay 2
V1
-
Position of local/remote position
0 = local + remote position
1 = local position
2 = remote position
V2
-
Resetting of audible alarm output
1 = reset
V3
-
Acknowledge of alarm signal
1 = acknowledge
V4
-
Testing
0 = testing off
1 = testing on