14
SAFERING XT/SAFEPLUS XT
—
4. Technical data
4.1 Electrical data SafeRing XT/SafePlus XT
Technical Data
C-Module
V-Module
SafeRing XT/SafePlus XT
Switch-
Disconnector
Earthing Switch Vacuum
circuit-breaker
Disconnector-
earthing switch
Rated voltage
kV
12
12
12
12
Power frequency
withstand voltage
kVrms
38
38
38
38
Across Disconnector/
Switch-Disconnector
kVrms
45
45
-
45
Lightening Impulse
withstand voltage
kVp
95
95
95
95
Across Disconnector/
Switch-Disconnector
kVp
110
110
-
110
Rated normal current
A
630
-
630
-
Rated frequency
Hz
50
50
50
50
Breaking capacities:
- Active load breaking
current
A
630
-
-
-
- Closed loop breaking
current
A
630
-
-
-
- Cable charging
breaking current
A
63
-
31.5
-
- Line charging breaking
current
A
1
-
10
-
- Earth fault breaking
current
A
190
-
-
-
- Cable and line charging
breaking current under
earth fault conditions
A
110
-
-
-
- Short circuit breaking
current
kA
-
-
21
-
Rated short circuit
making capacity
kAp
52.5
52.5
52.5
52.5
Short time current 3 sec
kA
21
21
21
21
Rated filling pressure
(Absolute) at 20°C
Mpa
0.13
Internal arc classification
IAC AFLR
kA/s
10/0.1
Internal arc classification
IAC AFLR
kA/s
21/1