SAFERING XT/SAFEPLUS XT
8.4 Cable Earthing arrangements:
Fix the cable earthing
B
properly with the holes provided
on the Aluzinc part in cable compartment.
B
8.3 Cable Clamping arrangements:
Adjustable cable clamping
A
arrangements suitable for
3Core Single Run cable.
Up & Down, ↕ Front & Rear ↔ Adjustment Possible
—
Figure 8.16
Cable clamping arrangements
A
—
Figure 8.17
cable earthing arrangements
8.5 Removal of Bottom cover
During Cable termination, remove the bottom cover of the
RMU for easy routing & pulling of cables.
Ensure once termination is completed bottom cover is
refixed with proper hardware as per table
WASH-N_ISO7089_8x16x1,6-PA6/NC
WASH-SP_DIN6796_8.4/18-X39CRM017-1/PL
HEX-HD-SCR_ISO4017_M8X20-A4-70/PL
—
Figure 8.18
Bottom cover details
8.6 Earthing Of RMU
Rear side earthing connections are provided on both end of
RMU for external earthing. Ensure Both earthing
connections are connected to external earthing.
(It is recommended to connect both earthing connections
together, if only one external earthing is available.)
—
Figure 8.19
RMU earthing arrangements