42
SAFERING XT/SAFEPLUS XT
—
16. Metering module
16.1 To get access to metering module
1. Unlock the front lock and then open the main door.
A
2. Get the direct access to metering module LV
compartment.
B
3. To get Access to High voltage compartment/
Voltage transformer compartment remove the
front mesh.
C
DANGER !
Make sure there is no voltage in the busbars and cable
terminals and that the risk of reconnection is eliminated
in all units. Any remote control must also be prevented.
DANGER !
Always check voltage presence before start
of any work inside M-module
NOTE
Ensure that HV fuse / dummy fuse is inserted properly into both upper
and lower fuse holder
A
C
B
—
Figure 16.1
RMU+Metering coupled unit
—
Figure 16.2
RMU+Metering coupled unit.
open door condition