Section 7
1MRK 511 434-UEN A
Technical Data
54
SAM600 Process Bus I/O System
Operation Manual
Interface
Connector
Pin
Remark
Power supply - VDC
X2
3
Digital interface
X10
Test switch indication
X10
1
Fuse failure phase 1
X10
2
Fuse failure phase 2
X10
3
Fuse failure phase 3
X10
4
Binary input of common GND
X10
5
Shielding GND
X10
6
Shielding GND
X10
7
Analog inputs
X20
Voltage phase L1-
X20
1
Voltage phase L1+
X20
2
Voltage phase L2-
X20
3
Voltage phase L2+
X20
4
Voltage phase L3-
X20
5
Voltage phase L3+
X20
6
Voltage phase N-
X20
7
Voltage phase N+
X20
8
Optical network interface
X101/X102
IEC/UCA 61850-9-2LE process
bus/system bus
X101
NA
SFP cage for optional 100Base-FX
SFP module
IEC/UCA 61850-9-2LE process
bus/system bus
X102
NA
SFP cage for optional 100Base-FX
SFP module
Electrical network interface
X103/X104
IEC/UCA 61850-9-2LE process
bus/system bus
X103
NA
100Base-TX
IEC/UCA 61850-9-2LE process
bus/system bus
X104
NA
100Base-TX
Configuration interface
X105
Connection to SAM600 configuration
tool
X105
NA
USB-A/USB-A cable
LED status indication
D2
Status indications
D2.1-D2.4
NA
For more details refer to
Section