Accessing the recorder connection terminals

Referring to Fig. 3:

1. Press the terminal cover release plate in recess

A

and

pull terminal cover

B

away from the recorder body to

expose the terminal connections.

Power supply connections

Referring to Fig. 4:

1. Make connections to the power supply terminals

(module position E) as follows:

AC supply: terminals 1 (line), 2 (neutral), 3 (ground)

or

DC supply: terminals 4 (+), 5 (–)

Fig. 3 Accessing the recorder connection terminals

Note.

Tighten terminal screws to a torque of

0.1 Nm (0.9 lbf.in).

Fig. 4 Power supply connections and fuse ratings

3

5

4

+

3

1

2

L

N

A

B

C

D

E

1

2

3

4

5

Warning

. Use fuse rating 500 mA (max.) Type T

(UL category JDYX2)

Warning

. Use fuse rating 2.5 A (max.) Type T

Neutral

Fuse 500 mA Type T IR = 100 A

Fuse

2.5 A Type T

AC Supply

DC Supply

100 to 240 V
50 / 60 Hz

24 V DC

Module positions

Power

supply
terminals –
see below

Line

AC power supply
earth (ground)
stud

6

CI/RVG200–EN

Summary of Contents for ScreenMaster RVG200

Page 1: ...values and fuse requirements 4 Navigation navigating the user interface quickly and effectively 5 Menus overview menu familiarization 6 Basic setup steps required for first time use 7 Symbols and ico...

Page 2: ...sure to isolate the supply before removing the terminal cover Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressure a...

Page 3: ...rsonal injury and or death The user should reference this instruction manual for operation and or safety information This symbol when noted on a product enclosure or barrier indicates that a risk of e...

Page 4: ...lectrical and magnetic fields If this is not possible particularly in applications where mobile communications equipment is expected to be used screened cables within flexible earthed metal conduit mu...

Page 5: ...e terminals accept cables from 0 8 to 2 5 mm2 18 to 14 AWG The recorder conforms to Installation Category II of IEC 61010 All connections to secondary circuits must have basic insulation After install...

Page 6: ...e 2 neutral 3 ground or DC supply terminals 4 5 Fig 3 Accessing the recorder connection terminals Note Tighten terminal screws to a torque of 0 1 Nm 0 9 lbf in Fig 4 Power supply connections and fuse...

Page 7: ...0 9 8 7 6 5 4 1 2 18 17 16 15 14 13 12 3 11 10 9 8 7 6 5 4 1 2 13 12 L N Tx Tx Tx Rx 3 11 10 9 8 7 6 5 4 1 2 18 17 16 15 14 13 12 Tx Rx 1 2 3 4 5 6 1 2 3 4 5 RJ45 USB Inputs 1 to 6 RTD R THC Volt free...

Page 8: ...e 2 of 2 Display Operator menu icons page 1 of 2 Exit Operator menus return to previous view Exit display Display associated menus Access dialog Accept settings Fig 8 Navigating groups and views Swipe...

Page 9: ...ed by pressing the icon associated with the required function Select Group Configuration Operator Message Logging Select View Historical Review Screen Interval Acknowledge Alarm Auto Group Scroll Stop...

Page 10: ...ation based on the instrument s default configuration Configuration menu options comprise Common Groups Channels I O Functions Logic Editor Maths equations System Configuration Common Setup Number of...

Page 11: ...nable Bar graph markers Menu enables Batch if option enabled Enable Batch Recording Start Stop Abort Operator Login Batch Number Field 1 3 Title Channels Setup Source ID Trace color Zone Filter type S...

Page 12: ...mentation Master Modbus TCP Port Poll Rate Poll fail limit Response Timeout Client Authorization TCP TCP Client Access Authorized IP 1 6 Comms analog I P Comms analog I P Protocol Comms Digital I P Co...

Page 13: ...ay the Group Configuration dialog Select the channel s to be assigned to each group When allocation is complete press to return to the Common Configuration level 6 4 Set up the archive files 1 Press t...

Page 14: ...ssociated with that module 3 Configure parameters for each required module 4 When all parameters have been configured press to return to the I O page then to return to the System Configuration page 5...

Page 15: ...ration change File deleted Archive media inserted Archive media removed Archive media offline Archive media online Archive media full System error reset archiving Daylight time or daylight saving star...

Page 16: ...he contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible...

Reviews: