Overhaul Instructions
Assembling the circuit-breaker and commissioning
1HSB435409-201 enrev1
35
10. Assembling the circuit-breaker and commissioning
The circuit-breaker is assembled and commissioned in accordance with the
applicable assembly instructions for the circuit-breaker in question.
After assembling the circuit-breaker, check and note down the operating values.
Check carried out on the:________________________________
First overhaul.
Check the following
Measured values
Pole A
Pole B
Pole C
Closing time coil I
ms
ms
ms
Closing time coil II
ms
ms
ms
Opening time coil I
ms
ms
ms
Opening time coil II
ms
ms
ms
Close-Open times
(1)
(1) The circuit-breaker must not be operated Open-Close without an intermediate delay of 300 ms.
ms
ms
ms
Lowest control voltage to coil I
V
V
V
Lowest control voltage to coil II
V
V
V
Lowest control voltage from coil I
V
V
V
Lowest control voltage from coil II
V
V
V
Main circuit resistance
µΩ
µΩ
µΩ
Filling pressure
(2)
(2) Filling pressure according to rating plate.
MPa (abs)
MPa (abs)
MPa (abs)