SM3000
Multipoint Videographic Recorder
7 Installation
IM/SM3000–EN Rev. L
119
7.8 Hybrid I/O Module Connections
7.8.1 Digital Output Connections
Six digital outputs are provided on the Hybrid option board.
7.8.2 Digital Input Connections
Six digital inputs are provided on Hybrid option boards.
7.8.3 Analog Output Connections
Two analog outputs are provided on the Hybrid option board.
Fig. 7.13 Digital Output Connections
Note.
Voltage level: 5 V.
Load:
450
min. 15 k
max.
Digital Output
Common
Load
9
10
11
12
13
14
15
16
do1
do2
do3
do4
do5
do6
COM
COM
Terminal Block E, F, G or H
Fig. 7.14 Digital Input Connections
Fig. 7.15 Analog Output Connections
di1
di2
di3
di4
di5
di6
COM
COM
Terminal Blocks E, F, G or H
Input State
Dxx active
Switch Input
or
or
5V
0V
Logic Input
Logic State
Dxx in-active
1
2
3
4
5
6
7
8
5V
or
0V
a01
a02
17
18
19
20
+
+