SM3000
Multipoint Videographic Recorder
Appendix B – Modbus Guide
162
IM/SM3000–EN Rev. L
Channel Number
Signal
3.7
3.8
3.9
3.10
3.11
3.12
Analog input value
R
5501 and 5502
5551 and 5552
5601 and 5602
5651 and 5652
5701 and 5702
5751 and 5752
Alarm A trip
R/W
5503 and 5504
5553 and 5554
5603 and 5604
5653 and 5654
5703 and 5704
5753 and 5754
Alarm B trip
R/W
5505 and 5506
5555 and 5556
5605 and 5606
5655 and 5656
5705 and 5706
5755 and 5756
Alarm C trip
R/W
5507 and 5508
5557 and 5558
5607 and 5608
5657 and 5658
5707 and 5708
5757 and 5758
Alarm D trip
R/W
5509 and 5510
5559 and 5560
5609 and 5610
5659 and 5660
5709 and 5710
5759 and 5760
Totalizer A max. flowrate
R
5511 and 5512
5561 and 5562
5611 and 5612
5661 and 5662
5711 and 5712
5761 and 5762
Totalizer B max. flowrate
R
5513 and 5514
5563 and 5564
5613 and 5614
5663 and 5664
5713 and 5714
5763 and 5764
Totalizer A min. flowrate
R
5515 and 5516
5565 and 5566
5615 and 5616
5665 and 5666
5715 and 5716
5765 and 5766
Totalizer B min. flowrate
R
5517 and 5518
5567 and 5568
5617 and 5618
5667 and 5668
5717 and 5718
5767 and 5768
Totalizer A average flowrate
R
5519 and 5520
5569 and 5570
5619 and 5620
5669 and 5670
5719 and 5720
5769 and 5770
Totalizer B average flowrate
R
5521 and 5522
5571 and 5572
5621 and 5622
5671 and 5672
5721 and 5722
5771 and 5772
Totalizer A batch total
R
5523 to 5526
5573 to 5576
5623 to 5626
5673 to 5676
5723 to 5726
5773 to 5776
Totalizer B batch total
R
5527 to 5530
5577 to 5580
5627 to 5630
5677 to 5680
5727 to 5730
5777 to 5780
Totalizer A max. flowrate
(previous batch)
R
5531 and 5532
5581 and 5582
5631 and 5632
5681 and 5682
5731 and 5732
5781 and 5782
Totalizer B max. flowrate
(previous batch)
R
5533 and 5534
5583 and 5584
5633 and 5634
5683 and 5684
5733 and 5734
5783 and 5784
Totalizer A min. flowrate
(previous batch)
R
5535 and 5536
5585 and 5586
5635 and 5636
5685 and 5686
5735 and 5736
5785 and 5786
Totalizer B min. flowrate
(previous batch)
R
5537 and 5538
5587 and 5588
5637 and 5638
5687 and 5688
5737 and 5738
5787 and 5788
Totalizer A average flowrate
(previous batch)
R
5539 and 5540
5589 and 5590
5639 and 5640
5689 and 5690
5739 and 5740
5789 and 5790
Totalizer B average flowrate
(previous batch)
R
5541 and 5542
5591 and 5592
5641 and 5642
5691 and 5692
5741 and 5742
5791 and 5792
Totalizer A batch total
(previous batch)
R
5543 to 5546
5593 to 5596
5643 to 5646
5693 to 5696
5743 to 5746
5793 to 5796
Totalizer B batch total
(previous batch)
R
5547 to 5550
5597 to 5600
5647 to 5650
5697 to 5700
5747 to 5750
5797 to 5800
Table B.33 Registers by Channel – Process Group 3, Channels 7 to 12