6 Configuration
IM/SM3000–EN Rev. L
51
6 Configuration
6.1 Introduction
This section details the configuration of the instrument locally
using the front panel membrane switches. A configuration file
can also be created on a PC and transferred to the instrument
via one of the archive media options.
In addition, up to 5 different configurations can be stored in
internal memory and restored when required.
6.1.1 Configuration Level Security
Two methods of configuration access protection are available:
1.
Password protection
(Factory Default).
The Configuration level cannot be accessed until the
correct password has been entered – see Fig. 6.1, page
52.
2.
Internal switch protection
.
The Configuration level cannot be accessed until the
instrument is withdrawn from its case and the internal
switch set to the 'Configuration Level Not Protected'
position – see Fig. 6.2, page 53.
6.1.2 Configuration Level Access – Figs. 6.1 and 6.2
To configure an instrument when 'Configuration security type' is
set to the factory default setting of 'Password protected':
Access the Configuration Level – see Fig. 6.1, page 52.
Make changes to parameters as detailed in Figs. 6.1
and 6.3.
To configure an instrument when 'Configuration security type' is
set to 'Internal switch protected':
Set the internal security switch to the 'Configuration Level
Not Protected' position – see Fig. 6.2, page 53.
Access the Configuration Level – see Fig. 6.1, page 52.
Make changes to parameters as detailed in Figs. 6.1
and 6.3.
'Configuration security type'
Parameter Setting
Internal Security Switch
Setting
'Password
protected'
(Factory Default)
'Internal switch
protected'
(Alternative)
Configuration Level
Protected
(Factory Default)
Password Access
No Access
Configuration Level Not
Protected
Free Access
Free Access