SM500F
Field mountable paperless recorder
7 Configuration
94
IM/SM500F Rev. Z
Select the color used to display the trace and its tag on Chart and
Indicator views. Trace colors can be selected from the following:
Magenta, Red, Black, Green, Blue, Brown, Cyan, Yellow, Light Green,
Dark Cyan, Dark Yellow, Dark Blue.
Note.
On a monochrome recorder, all traces appear in black but the
recorder's in-built web server displays all traces in color on a PC monitor.
Each recording channel can be configured to position its trace in one of 9
specific zones in the Chart views in order to separate traces that would
otherwise be very close to each other.
Select one of the pre-defined zones available.
Select the filter to be applied to the electrical input prior to sampling.
Note.
Applicable to analog sources only.
Filters are applied to the recorded values shown on the Chart view
only, not to instantaneous values displayed on the channel
indicators.
Instantaneous – A single value based on process conditions at the
time of sampling.
Average
– The average value of the analog signal since the
previous sample.
Minimum
– The minimum value of the analog signal since the
previous sample.
Maximum
– The maximum value of the analog signal since the
previous sample.
Max & min
– Two values are recorded to capture the maximum &
minimum signal values since the previous sample.
This allows the memory use to be extended by
permitting a slower sample rate to be selected
without losing the transient behavior of the signal.
•1
If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.
1