Function block
SPA address CMD Input
SPA address CMD output
SINGLECMD3-Cmd16
4-S-4720
5-O-558
SINGLECMD4-Cmd1
4-S-4738
5-O-559
SINGLECMD4-Cmd2
4-S-4739
5-O-560
SINGLECMD4-Cmd3
4-S-4740
5-O-561
SINGLECMD4-Cmd4
4-S-4741
5-O-562
SINGLECMD4-Cmd5
4-S-4742
5-O-563
SINGLECMD4-Cmd6
4-S-4743
5-O-564
SINGLECMD4-Cmd7
4-S-4744
5-O-565
SINGLECMD4-Cmd8
4-S-4745
5-O-566
SINGLECMD4-Cmd9
4-S-4746
5-O-567
SINGLECMD4-Cmd10
4-S-4747
5-O-568
SINGLECMD4-Cmd11
4-S-4748
5-O-569
SINGLECMD4-Cmd12
4-S-4749
5-O-570
SINGLECMD4-Cmd13
4-S-4750
5-O-571
SINGLECMD4-Cmd14
4-S-4751
5-O-572
SINGLECMD4-Cmd15
4-S-4752
5-O-573
SINGLECMD4-Cmd16
4-S-4753
5-O-574
shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
IED for control of a circuit breaker.
A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in
SINGLECMD:1 are shown in table
.
SINGLECMD
BLOCK
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
AND
INPUT1
INPUT2
INPUT3
INPUT4
OUT
NOUT
PULSETIMER
INPUT
OUT
#CD01-CMDOUT1
#CD01-CMDOUT2
#CD01-CMDOUT3
#CD01-CMDOUT4
#CD01-CMDOUT5
#CD01-CMDOUT6
#CD01-CMDOUT7
#CD01-CMDOUT15
#CD01-CMDOUT16
#CD01-CMDOUT8
#CD01-CMDOUT9
#CD01-CMDOUT10
#CD01-CMDOUT11
#CD01-CMDOUT12
#CD01-CMDOUT13
#CD01-CMDOUT14
SYNCH OK
PULSETIMER
INPUT
OUT
To output board, CLOSE
To output board, OPEN
IEC05000717-4-en.vsd
IEC05000717 V4 EN-US
Figure 3:
Application example showing a simplified logic diagram for control
of a circuit breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady
or setable pulse length signals. This is set in Parameter Setting Tool (PST) under:
Section 3
1MRK 511 418-UEN A
SPA operation principle
16
650 series 2.2 IEC
Communication protocol manual