59
When the IEC 61850 client has been notified of the incoming record, the
client should read the COMTRADE files from SPA-ZC 400 by using FTP or
IEC 61850 File Transfer connection. The client must remove the files after
successful reading to maintain free space for forthcoming records. The files
are named as follows:
File name
Example
Description
yymmddnn.cfg
70010104.cfg
Configuration file
yymmddnn.dat
70010104.dat
Data file
yymmddnn.inf
70010104.inf
Information file
The filename consists of the following parts:
Part
Format
Description
yy
00
–
99
Record creation timestamp, year
mm
01
–
12
Record creation timestamp, month
dd
01
–
31
Record creation timestamp, date
nn
00 - 99
Running serial number of the records of
the same day. The Configuration, Data
and Information files related to one
record have the same serial number.
1MRS755347
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 400