background image

97

Table 11.2.2.18.-1 Controllable integer status (INC)

INC class

Attribute
Name

Attribute Type

FC

TrgOp

Value/ Value
range

M/O/C

SPA-ZC 400/
Comments

DataName

Inherited from Data Class (refer to IEC 61850-7-2)

Supported

DataAttribute

Control and Status

ctlVal

CtxInt

CO

AC_CO_M

Supported

operTm

TimeStamp

CO

AC_CO_O

Not Supported

origin

Originator

ST

AC_CO_O

Not Supported

ctlNum

INT8U

ST

0..255

AC_CO_O

Not Supported

stVal

INT32

ST

dchg

M

Supported

q

Quality

ST

qchg

M

Supported

t

TimeStamp

ST

M

Supported

stSeld

BOOLEAN

ST

dchg

AC_CO_O

Not Supported

Substitution

subEna

BOOLEAN

SV

PICS_SUBST Not Supported

subVal

ValWithTrans

SV

PICS_SUBST Not Supported

subQ

Quality

SV

PICS_SUBST Not Supported

subID

VISIBLE
STRING64

SV

PICS_SUBST Not Supported

Configuration, Description and Extension

persistent

BOOLEAN

CF

M

Not Supported

ctlModel

ENUMERATED

CF

Status-only |
direct-with-
normal-security
| sbo-with-
normal-security
| direct-with-
enhanced-
security | sbo-
with-enhanced-
security

M

Supported

sboTimeout

INT32U

CF

AC_CO_O

Not Supported

sboClass

ENUMERATED

CF

operate-once |
operate-many

AC_CO_O

Not Supported

minVal

INT8

CF

O

Not Supported

maxVal

INT8

CF

O

Not Supported

stepSize

INT8U

CF

1 ... (maxVal -
minVal)

O

Not Supported

d

VISIBLE
STRING255

DC

Text

O

Supported

1MRS755347

Ethernet Adapter

SPA to IEC 61850 Gateway

Installation and Commissioning Manual

SPA-ZC 400

Summary of Contents for SPA-ZC 400

Page 1: ...Ethernet Adapter SPA ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual ...

Page 2: ......

Page 3: ...x 23 5 2 3 Uninstalling Communication Engineering Tool for SPA ZC 40x 25 5 3 Installing Connectivity Packages 25 5 3 1 Enabling Connectivity Packages 26 5 3 2 Uninstalling Connectivity Packages 27 5 4 Connecting to SPA ZC 400 27 5 4 1 Changing computer s IP address 27 5 4 2 Checking connection to SPA ZC 400 28 6 Engineering 31 6 1 Overview of engineering 31 6 2 Creating project 32 6 3 Restarting 3...

Page 4: ...3 Using Disturbance Recorder files 58 7 Commissioning 61 7 1 Checking SPA communication 61 8 Technical data 63 8 1 Interfaces 63 8 2 Test and conditions 65 9 Maintenance and service 67 9 1 LED indicators 67 9 2 Communication settings 67 9 3 IP Query 69 9 4 Identification 70 9 5 Obtaining error logs 71 10 Troubleshooting 73 11 Technical reference 75 11 1 ACSI conformance statement 75 11 2 Model con...

Page 5: ...4 11 2 2 17 Controllable double point DPC 95 11 2 2 18 Controllable integer status INC 96 11 2 2 19 Binary controlled step position information BSC 98 11 2 2 20 Integer controlled step position information ISC 99 11 2 2 21 Controllable analogue set point information APC 101 11 2 2 22 Single point setting SPG 101 11 2 2 23 Integer status setting ING 102 11 2 2 24 Analogue setting ASG 103 11 2 2 25 ...

Page 6: ...13 Ordering information 115 14 Terminology 117 15 Abbreviations 119 6 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 7: ...not be reproduced or copied without written permission from ABB Oy and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose The software or hardware described in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Copyright 2006 ABB Oy All rights reserved Trademarks ABB is a reg...

Page 8: ...8 ...

Page 9: ...ls This publication includes the following icons that point out safety related conditions or other important information The electrical warning icon indicates the presence of a hazard which could result in electrical shock The caution icon indicates important information or warning related to the concept discussed in the text It might indicate the presence of a hazard which could result in corrupt...

Page 10: ...language for communication in electrical substations related to IEDs IEC 61850 7 2 Basic communication structure for substation and feeder equipment Abstract communication service interface ACSI IEC 61850 7 3 Basic communication structure for substation and feeder equipment Common data classes IEC 61850 7 4 Basic communication structure for substation and feeder equipment Compatible logical node c...

Page 11: ...e buttons are boldfaced For example click OK The names of menus and menu items are boldfaced For example the File menu The following convention is used for menu operations Menu Name Menu Item Cascaded Menu Item For example select File Open New Project The Start menu name always refers to the Start menu on the Windows Task Bar System prompts messages and user responses input are shown in the Courie...

Page 12: ...12 ...

Page 13: ...out the electrical installation National and local electrical safety regulations must always be followed The device contains components which are sensitive to electrostatic discharge Unnecessary touching of electronic components must therefore be avoided 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 400 ...

Page 14: ...14 ...

Page 15: ...e appropriate Connectivity Package by using Connectivity Package Manager see Fig 3 1 A060282 Fig 3 1 Connectivity Package Manager 3 Create a new project by selecting File Open Manage Project from CET for SPA ZC 40x 4 Install a new IEC 61850 device SPA ZC 40x by right clicking the project and selecting New IEC61850 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning ...

Page 16: ...ging computer s IP address 8 Set Time Zone Correction 9 Rename the IED for example REF545_F1 10 Adjust IED SPA Communication parameters in the Object Properties pane 11 Adjust network adapter s IP address to same subnet as SPA ZC 400 To perform the operation open Windows XP Network Connections in Control Panel If CID file exists the IP address is read from the file Otherwise the default IP address...

Page 17: ...0 REL 511 REX 521 REF 543 A060009 Fig 4 1 Conceptual picture of a typical system setup The mechanical and electrical connection of the Ethernet adapter to a REF 541 3 5 REM 543 5 or RET 541 3 5 interface is described in Section 5 Installation The Ethernet adapter programming is described in Section 6 Engineering It is a prerequisite to understand the communication properties of Intelligent Electro...

Page 18: ...pending on whether the light is turned on or off In the loop topology the interface receives the message from the fibre optic interface and passes it both to the fibre optic transmitter and to the RS 485 interface In the star topology the interface receives the message from the fibre optic receiver and passes it only to the RS 485 interface If the message is received from the RS 485 interface it i...

Page 19: ...gh SPA ZC 400 The process data status measurements and commands is routed through the IEC 61850 bus and the rest of the available data can be routed through SPA over TCP IP Only one SPA client can be configured to poll SPA events from the device By default SPA ZC 400 is configured to poll SPA events then it is not allowed to poll SPA events from another SPA client If the event polling is disabled ...

Page 20: ...s one protocol which answers to all requirements in substation The configuration of the protocol is flexible When using the IEC 61850 standard it is possible to allocate the functions and integrate the functionality freely The IEC 61850 standard supports the following functions Protection and control Integration of innovative sensor and switch technologies Metering supervisory control and data acq...

Page 21: ...unication standards for substation automation the IEC 61850 standard defines data modeling and communication services for this specific domain Data modeling is mapped to a communication protocol Manufacturing Message Specification MMS ISO 9506 protocol which uses TCP IP and Ethernet In addition to the communication specifications engineering information exchange is defined in Substation Configurat...

Page 22: ...22 ...

Page 23: ... running one of these operating systems is sufficient also for CET for SPA ZC 40x For more information refer to Section 1 4 Product documentation The detailed system requirements can be seen below 20 MB free hard disk space if Microsoft NET Framework 1 1 which is required for running CET for SPA ZC 40x has already been installed 100 MB free hard disk space if the Microsoft NET Framework 1 1 is not...

Page 24: ...e manual and select Entire feature will be installed on local hard drive To install the manual when required click the respective manual and select Feature will be installed when required Not to install the manual click the respective manual and select Entire feature will be unavailable 9 Click Next to begin the installation 10 Follow the progress of the installation in a dialog that also shows th...

Page 25: ...insert the SPA ZC 400 configuration CD to the CD ROM drive of your PC The Connectivity Packages can be downloaded on the ABB web site http www abb com substationautomation Contact ABB to check the connectivity package s status for the Intelligent Electronic Device IED in question 2 Double click the Connectivity Package installation program and select the relevant IED msi to start the installation ...

Page 26: ...tion in a dialog which also shows the directory path where the files are copied to At this point you can still cancel the installation by clicking Cancel 9 A dialog opens to show that the Connectivity Package has been successfully installed Close the dialog and finish the installation by clicking Finish After installing a new CET for SPA ZC 40x version or new Connectivity Packages always activate ...

Page 27: ...ckage and click Remove 5 4 Connecting to SPA ZC 400 The Sections 5 4 1 and 5 4 2 Checking connection to SPA ZC 400 describe how to connect to SPA ZC 400 from the Communication Engineering Tool CET for SPA ZC 40x 5 4 1 Changing computer s IP address To connect SPA ZC 400 the used computer and SPA ZC 400 must use the same address space 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installatio...

Page 28: ...8 2 1 See Fig 5 4 1 1 You must have system administration rights to perform the task A060241 Fig 5 4 1 1 Changing IP address 5 4 2 Checking connection to SPA ZC 400 Check the connection to SPA ZC 400 by using the ping command 1 Open the Run dialog 2 Type cmd to the Open box see Fig 5 4 2 1 28 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 29: ...4 2 2 Pinging SPA ZC 400 SPA ZC 400 responds to the ping command if the computer and SPA ZC 400 are on the same network 5 If SPA ZC 400 responds with the IP address the connection is established between the computer and SPA ZC 400 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 400 ...

Page 30: ...30 ...

Page 31: ... the IEC 61850 standard The communication structure consist of Logical devices LD Logical nodes LN Data objects DO Data attributes DA The data model is imported from the preconfigured object types of devices which have the objects defined and configured These object types are defined in the standardized IED Connectivity Packages The data model can also be created manually by using CET for SPA ZC 4...

Page 32: ...1 Opening a project A040014B Fig 6 2 2 Creating a new project 6 3 Restarting Use this function to restart the SPA ZC 400 at runtime 1 Select IED and Tools Reset Tool to open the restart pane see Fig 6 3 1 2 Click Reset The results are reported to the UI text box 32 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 33: ...ure an object tree in the Communication Engineering Tool CET for SPA ZC 40x to define the communication structure Fig 6 4 1 shows an example of the object tree when it has been built In the example tree you can see the SPA ZC 400 object and its child objects as devices and data objects Indentation is used to indicate the parent child relationship between the objects 1MRS755347 Ethernet Adapter SPA...

Page 34: ... to select the object to which you want to add a child object You can copy the object You can select the object using a drag and drop operation Add the objects in the following order 1 IEC 61850 Device object SPA ZC 40x 2 Logical Device objects 3 Logical Node objects 4 Data objects 5 Datasets 6 Reporting control blocks 34 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commis...

Page 35: ...or each device A040023B Fig 6 4 1 1 Adding an IEC 61850 Device object Ensure that the new IED name is unique within the planned network by renaming the IED for example REF545_F1 A Tunneling Device object cannot be configured for an IEC 61850 gateway 6 4 2 Adding Logical Device objects Communication Engineering Tool CET creates logical device LD0 automatically for SPA ZC400 when creating a new IED ...

Page 36: ...ter you have installed Connectivity Packages to your computer The IED s data model behind SPA ZC 400 is described in the logical device LD1 For more information about installing Connectivity Packages refer to Section 5 3 Installing Connectivity Packages A040024B Fig 6 4 2 1 Adding Logical Device objects The logical device object is now shown as a sub object to the IEC 61850 Device object see Fig 6...

Page 37: ...pport all the functions of IED The functions which are not mapped to the IEC 61850 structure are reported after import The tool imports default data sets and report control blocks RCB to logical device LD0 see Fig 6 4 3 1 Data sets include a set of selected data attributes from IED s IEC 61850 data model These data sets are used in the IEC 61850 event reporting model If data attributes are selecte...

Page 38: ...You can modify dataset by using Dataset Editor Open Dataset Editor by selecting the dataset and right click to open Dataset Editor Dataset has a set of data attributes logical device instance name optional prefix logical node instance name logical node class data object name and functional constraint FC Functional constraint divides data attributes to groups which have the same functional constrai...

Page 39: ...te function A040028 Fig 6 5 1 Dataset Editor Dataset Editor columns IdInst Instance of Logical Device to which referenced dataset belongs Prefix Freely configurable part of LN Caption InInst Instance of the LN type Class of the LN type InClass doName Name of the data object from which dataset is formed daName Name of the data attribute from which dataset is formed from fc Identifies the signal mea...

Page 40: ...ameters SPA ZC 400 communication parameters are located in the device properties SPA ZC 400 uses static IP addresses which have to be defined in the planned network structure IP Address IP address identifies SPA ZC 400 in Local Area Network LAN All communication via SPA ZC 400 uses this address The default value is 192 168 2 10 and it has to be changed to a unique address according to the planned ...

Page 41: ... device has SPA Communication Parameters Object properties except LD0 which describes the SPA ZC 400 The SPA Address object property has to be the same as the configured SPA unit number in IED SPA Password SPA Password is used for commands and it has to be the same as the defined password in the IED SPA ZC 400 has to know the SPA Password to write the data to IED Password SPA parameter 0V160 is ne...

Page 42: ...rce is IED IED gets the time from external source Event poll If the parameter is disabled SPA ZC 400 does not poll event from IED and the IEC 61850 events are based on continuous data poll This feature could be used in systems where for example other REF 543 port is used already for the SPA communication By default the feature is disabled that is event polls are used DR Upload When this parameter ...

Page 43: ...s 192 168 2 10 to new IP address according to the planned network structure When the new configuration to SPA ZC 400 is downloaded Communication Engineering Tool CET checks if the basic IP addresses are changed If a change is detected CET asks whether new addresses are taken into use If the changes are not accepted SPA ZC 400 uses the old IP address from the previous configuration The IP addresses...

Page 44: ... function tries to determine the SPA ZC 400 version and exports the export file accordingly If the connection is disabled prompt the correct version to be exported see Fig 6 8 2 A060129 Fig 6 8 2 Selecting correct SPA ZC 400 version to be exported 44 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 45: ... be configured manually You can start building the IEC 61850 data model by creating an empty logical device For more information about adding logical device refer to Section 6 4 2 Adding Logical Device objects The IEC 61850 standard defines a mandatory logical node LLN0 for every device and its objects For best practice check some ready projects based on Connectivity Packages Adding and configurin...

Page 46: ...izard to start the DO Wizard see Fig 6 9 2 7 Select the DOType Depending on the DOType selected corresponding data attributes are automatically added 8 Type the DOI name 9 Click Add DOI button for every data object you add 46 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 47: ...ealth Health LPL_simple NamPlt INC_simple test For more information about data objects refer to Section 11 2 Model conformance statement 11 Define properties to the data objects In order to map the added IEC 61850 data objects to the SPA data model you have to define the properties for each data object 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA Z...

Page 48: ... in the Object Properties window The stVal field in the DOI editor is automatically updated with the data entered in the Object Properties Follow the same procedure for all data objects that you have added to the LN object A040133B Fig 6 9 3 Data Object Instance Editor The SPA point data is written to the sAddr in the CID file for the selected data object SPA ZC 400 uses this field to poll data an...

Page 49: ...Real Data A060032 Fig 6 10 1 Reporting model RCB s have the following properties To edit the properties right click the dataset and select Properties Buffered reporting IEC 61850 buffers events also during the communication break Buffer Time Default value for buffered reporting is 100 milliseconds ms With this value RCB waits 100 ms for other events after the first change before sending the report...

Page 50: ...stances If you define two clients for buffered reporting then Max has to be 2 SPA ZC 400 creates two instances of RCB name for example rcbStatNrml01 and rcbStatNrml02 For unbuffered reporting Max has to be same as the number of defined clients or higher This is defined in the IEC 61850 standard Trigger Options Data Change Data Update and Quality Change triggers are used by default changes in value...

Page 51: ...CB instance rcb name 01 and the second RCB uses second instance rcb name 02 It is not mandatory to define clients in unbuffered reporting but it is recommended for clarity Client IED Name has to match with the client name in Substation Configuration description Language SCL Every modification in RCB increases the rcb Configuration Revision property by one Each revision generates the CID file and t...

Page 52: ... The data is sent between IED and SPA ZC 400 Therefore it is possible to send and receive 32 single bits horizontal data In GOOSE sending data is based on dataset and GOOSE Control Block GoCB Dataset defines what kind of data is sent in the GOOSE frame GoCB links the GOOSE Control Block structure and its information to data The GoCB attributes are Multicast address A multicast address can be used ...

Page 53: ...taset 1 Create and rename it refer to Section 6 5 Using Dataset Editor 2 Drag and drop the data objects in Dataset Editor The data attributes that are not needed must be deleted in this phase for example the t attribute which is normally not needed in horizontal communication The GOOSE dataset is exported from the attribute level and therefore the Data Object structures are not sent When sending C...

Page 54: ... many IEDs for example enter interlock to the MAC Address field Grouping MaxTime and MinTime are not configurable MinTime indicates the maximum response time in milliseconds to data change Time can vary depending on the data type the default value is 100 ms MaxTime indicates the background heartbeat cycle time in milliseconds the default value is 10000 ms If the system uses VLAN it is possible to ...

Page 55: ...3 To attach inputs to a selected IED drag and drop a sending GoCB from another IED directly to Inputs Editor or select GoCBs in Signal Mapping tool Refer to Section 6 11 2 2 GOOSE RX specific features Signal Mapping tool shows IEDs and GoCBs in a matrix where the rows represent all possible GoCBs and the columns IEDs in the currently open project To receive specific data to a specific IED select t...

Page 56: ...e frame is not received the quality of the whole received dataset is set to bad and the input value is set to the default one defined in Inputs TAL times below 1000 ms are not counted 6 12 Scales To create a scale 1 If a Scales object does not exist in the object tree add the object by right clicking the project and selecting New Communication Generic ScaleGroup Object or import a Connectivity Pac...

Page 57: ...132 Fig 6 12 2 Configuring properties 5 Create reference to scale at DO level in object tree see Fig 6 12 3 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 400 ...

Page 58: ...newer SPA ZC 400 can load the recorded data and convert it to standard COMTRADE files in year 1999 format The conversion is done automatically and the Disturbance Recorder Ready signal is sent to IEC 61850 client after new files are ready to be read A relay with compatible MEDREC16 function block notifies SPA ZC 400 when it has new recordings ready SPA ZC 400 reads the actual data from the relay a...

Page 59: ...70010104 cfg Configuration file yymmddnn dat 70010104 dat Data file yymmddnn inf 70010104 inf Information file The filename consists of the following parts Part Format Description yy 00 99 Record creation timestamp year mm 01 12 Record creation timestamp month dd 01 31 Record creation timestamp date nn 00 99 Running serial number of the records of the same day The Configuration Data and Informatio...

Page 60: ...60 ...

Page 61: ...h stVal 1 OK configuration is completed successfully 2 Warning no clock synchronization 3 Alarm during the configuration appeared errors If the configuration fails check the error log files from the SPA ZC 400 file system The status and error logs are located in the log directory For more information about maintenance refer to Chapter 9 Maintenance and service 7 1 Checking SPA communication If the...

Page 62: ...objects indicate GOOD or DEFAULTED If this is not the case configurations between SPA ZC 400 and REF 541 3 5 REM 543 5 or RET 541 3 5 are not identical If all the data objects have INVALID quality the SPA communication is not running 62 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 63: ...LAN connector LON SPA interface Optional Fibre optic connector options ST multimode glass fibre transmitter receiver pair or snap in multimode plastic fibre transmitter receiver pair Optical fibres See fibre optic guides SPA ZF Optical glass fibres multimode graded index type Plastic core fibre optic cables features and instructions for mounting For more information see Section 1 4 Product documen...

Page 64: ...X DIAG LAN SERVICE PIN ETHERNET RX TX PLASTIC GLASS IEC 61850 MODBUS TCP SPA TCP A040130B Fig 8 1 1 Dimensions of the SPA ZC 400 module Table 8 1 1 Dimensions and weight Type Dimensions mm Weight g SPA ZC 400 195 x 50 x 26 130 64 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 65: ...erference tests Conducted common mode According to the IEC 61000 4 6 and IEC 60255 22 6 10 V rms f 150 kHz 80 MHz Radiated amplitude modulated According to the IEC 61000 4 3 and IEC 60255 22 3 10 V m rms f 80 1000 MHz Radiated pulse modulated According to the ENV 50204 and IEC 60255 22 3 10 V m f 900 MHz Fast transient disturbance tests According to the IEC 60255 22 4 and IEC 61000 4 4 All termina...

Page 66: ...g to the IEC 60255 21 1 class I Shock and bump test According to the IEC 60255 21 2 class I Table 8 2 4 Standard tests Supply current consumption Running 340 mA Start up 430 mA 66 SPA ZC 400 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755347 ...

Page 67: ...K configuration in use Configuration error RX Green On Indication for incoming LON traffic LON and SPA Possible sequences are 1 3 5 Normal situation 1 2 Missing boot image 1 3 4 Configuration file is missing 1 3 6 Configuration error If configuration error is detected because of the mismatches in downloaded the CID file download a simpler configuration Check also the log file in SPA ZC 400 9 2 Com...

Page 68: ...ET 541 3 5 Connectors Communication parameters X3 2 Protocol 2 X3 3 Protocol 3 Front connector SPA SMS LON SPA SPA SMS SPA IEC 60870 5 103a LON SPA IEC 60870 5 103b SPA SMS IEC 60870 5 103c SPA DNP 3 0d LON SPA DNP 3 0e SPA SMS DNP 3 0f SPA Modbus LON SPA Modbus SPA SMS Modbus SPA SPA SPA IEC 61850g LON SPA IEC 61850h SPA a Not included in REM 543 5 b Not included in REM 543 5 c Not included in RE...

Page 69: ...version information Example S e n d i n g I P q u e r y 1 R E C E I V E D M E S S A G E F R O M 1 0 5 8 1 2 5 1 5 1 M a c A d d r e s s 0 0 0 C 0 2 B 0 0 4 8 9 S u b n e t M a s k 2 5 5 2 5 5 2 5 5 0 D e f a u l t G a t e w a y 1 0 5 8 1 2 5 1 5 0 S N T P s e r v e r s 1 0 5 8 1 2 5 1 5 0 1 2 7 0 0 1 S W _ S P A T Y P E S P A Z C 4 0 x S W _ N U M B E R 1 M R S 1 1 8 5 3 3 S W _ B U I L D 1 1 0 S ...

Page 70: ...ed If version 2 0 is used MAC address other address and revision information is displayed 9 4 Identification If contacting the Customer Service it is necessary to send the following information by request Version of Connectivity Packages The version can be checked from the Connectivity Package Manager Version information of Communication Engineering Tool CET for SPA ZC 40x 70 SPA ZC 400 Ethernet A...

Page 71: ...et the correct version information from the device memory For more information about IP query refer to Section 9 3 IP Query 9 5 Obtaining error logs The following session transfers error log file through ftp C f t p x x x x User abb Password abb f t p c d l o g f t p g e t e r r o r l o g f t p q u i t 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA Z...

Page 72: ...72 ...

Page 73: ...irewall Table 10 1 TCP IP and UDP ports TCP UDP SPA Over TCP and CET tool IP Query port 7001 7001 FTP file transfer protocol ports 21 20 IEC 61850 communication protocol port 102 Network time management protocol port 123 Modbus TCP port 502 Windows XP SP 2 contains built in firewall 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 400 ...

Page 74: ...74 ...

Page 75: ...ntation Conformance Statement PICS and Model Implementation Conformance Statement MICS Notations For the following clauses the following definitions apply Table 11 1 Notations M m Mandatory support The item must be implemented C c Conditional support The item must be implemented if the stated condition exists O o Optional support The implementation may decide to implement the item x The implementa...

Page 76: ...n Conformance Statement MICS is defined detailing the standard data object model elements supported by SPA ZC 400 It is also possible to export the information in MICS to a CID file The CID file can be used in the system tool see Safety information Some of the data cannot be retrieved from the IED but it is the default value in the SPA ZC 400 11 2 1 Common data attribute classes 11 2 1 1 Quality T...

Page 77: ...ute is Not Supported The mapping may specify to exclude the attribute from the message if it is Not Supported or if the DEFAULT value applies 11 2 1 2 Analogue value Table 11 2 1 2 1 Analogue value AnalogueValue Type Definition Attribute Name AttributeType Value Value Range M O C SPA ZC 400 Comments I INT32 integer value GC_1 Not Supported f FLOAT 32 floating point value GC_1 Supported 11 2 1 3 Co...

Page 78: ...1 Step position with transient indication OriginatorType Definition Attribute Name AttributeType Value Value Range M O C SPA ZC 400 Comments orCat ENUMERATED not supported bay control station control remote control automatic bay automatic station automatic remote maintenance process M Supported orIdent OCTET STRING64 M Supported Table 11 2 1 6 2 Values for orCat Value Explanation bay control Contr...

Page 79: ...ge M O C SPA ZC 400 Comments SIUnit ENUMERATED According to table in Annex A M Supported multiplier ENUMERATED According to table in Annex A O Supported 11 2 1 8 Vector definition Table 11 2 1 8 1 Vector Vector Type Definition Attribute Name AttributeType Value Value Range M O C SPA ZC 400 Comments mag AnalogueValue M Supported ang AnalogueValue O Not Supported 11 2 1 9 CTxInt Context specific Int...

Page 80: ...xt O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported 11 2 2 2 Double point status DPS The table 11 2 2 2 1 defines the common data class of double point status Table 11 2 2 2 1 Double point status DPS DBS class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA Z...

Page 81: ...S Table 11 2 2 3 1 defines the common data class of integer status Table 11 2 2 3 1 Integer status INS INS class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Status stVal CtxInt ST dchg M Supported q Quality ST qchg M Supported t TimeStamp ST M Supported Substitution subEna BOOLE...

Page 82: ...alue Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Status general BOOLEAN ST dchg M Supported phsA BOOLEAN ST dchg O Supported phsB BOOLEAN ST dchg O Supported phsC BOOLEAN ST dchg O Supported neut BOOLEAN ST dchg O Supported q Quality ST qchg M Supported t TimeStamp ST M Supported Configuration Description and Extension ope...

Page 83: ... BOOLEAN ST dchg M Supported dirGeneral ENUMERATED ST dchg unknown forward backward both M Supported PhsA BOOLEAN ST dchg GC_2 1 Supported dirPhsA ENUMERATED ST dchg unknown forward backward GC_2 1 Supported PhsB BOOLEAN ST dchg GC_2 2 Supported dirPhsB ENUMERATED ST dchg unknown forward backward GC_2 2 Supported PhsC BOOLEAN ST dchg GC_2 3 Supported dirPhsC ENUMERATED ST dchg unknown forward back...

Page 84: ... 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Status cnt INT32U ST dchg M Not Supported sev ENUMERATED ST unknown critical major minor warning M Not Supported T TimeStamp ST M Not Supported addr OCTET STRING64 ST O Not Supported addInfo VISIBLE STRING64 ST O Not Supported Configuration Description and Extension D VISIBLE STRING255 DC O Not Supp...

Page 85: ...2 1 Not Supported frRds BOOLEAN CF GC_2 1 Not Supported d VISIBLE STRING255 DC O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 8 Measured value MV Table 11 2 2 8 1 defines the common data class of measured value Table 11 2 2 8 1 Measured value MV MV class Attribute Name A...

Page 86: ... INT32U CF 0 100 000 O Not Supported sVC ScaledValue Config CF AC_SCAV Not Supported rangeC RangeConfig CF GC_CON Not Supported smpRate INT32U CF O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist base...

Page 87: ...PICS_SUBST Not Supported subID VISIBLE STRING64 SV PICS_SUBST Not Supported Configuration Description and Extension units Unit CF see Annex A O Supported db INT32U CF 0 100 000 O Not Supported zeroDb INT32U CF 0 100 000 O Not Supported rangeC RangeConfig CF GC_CON Supported magSVC ScaledValue Config AC_SCAV Not Supported angSVC ScaledValue Config AC_SCAV Not Supported angRef ENUMERATED CF V A othe...

Page 88: ...1 Supported neut CMV GC_1 Supported net CMV GC_1 Not Supported res CMV GC_1 Not Supported DataAttribute Configuration Description and Extension angRef ENUMERATED CF Va Vb Vc Aa Ab Ac Vab Vbc Vca Vother Aother O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX A...

Page 89: ...EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the CMV type variant 11 2 2 12 Sequence SEQ Table 11 2 2 12 1 defines the common data class of sequence Table 11 2 2 12 1 Sequence SEQ SAV class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Co...

Page 90: ...te Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Measured Values Basics q Quality MX qchg M Not Supported t TimeStamp MX M Not Supported Harmonics and Interharmonics har ARRAY 0 numHar OF Vector MMX dchg dupd M Not Supported Configuration Description and Extension numHar INT16U CF 1 M N...

Page 91: ... Harmonic value for WYE HWYE Table 11 2 2 14 1 defines the common data class of harmonic value for WYE Table 11 2 2 14 1 Harmonic value for WYE HWYE HWYE class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Measured Values Basics q Quality MX qchg M Not Supported t TimeStamp MX...

Page 92: ...t Supported angRef ENUMERATED CF Va Vb Vc Aa Ab Ac Vab Vbc Vca Vother Aother O Not Supported smpRate INT32U CF O Not Supported frequency FLOAT32U CF fundamental frequency M Not Supported hvRef ENUMERATED CF fundamental rms absolute O Not Supported rmsTim INT32U CF AC_RMS_M Not Supported d VISIBLE STRING255 DC Text O Not Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE ...

Page 93: ...Description and Extension numHar INT16U CF 1 M Not Supported numCycl INT16U CF 0 M Not Supported evalTim INT16U CF M Not Supported units Unit CF see Annex A O Not Supported angRef ENUMERATED CF Va Vb Vc Aa Ab Ac Vab Vbc Vca Vother Aother O Not Supported smpRate INT32U CF O Not Supported frequency FLOAT32U CF fundamental frequency M Not Supported hvRef ENUMERATED CF fundamental rms absolute O Not S...

Page 94: ...T qchg AC_ST Supported t TimeStamp ST AC_ST Supported stSeld BOOLEAN ST dchg AC_CO_O Not Supported Substitution subEna BOOLEAN SV PICS_SUBST Not Supported subVal BOOLEAN SV FALSE TRUE PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRIN64 SV PICS_SUBST Not Supported Configuration Description and Extension pulseConfig PulseConfig CF AC_CO_O Not Supported ctlModel EN...

Page 95: ...trollable double point DPC SPC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class see IEC 61850 7 2 Supported DataAttribute Control and Status ctlVal BOOLEAN CO off FALSE on TRUE AC_CO_M Supported operTm TimeStamp CO AC_CO_O Not Supported origin Originator ST AC_CO_O Supported ctlNum INT8U ST 0 255 AC_CO_O Supported stVal COD...

Page 96: ...sboTimeout INT32U CF AC_CO_O Not Supported sboClass ENUMERATED CF operate once 0 operate many 1 AC_CO_O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the connectivity package short address ...

Page 97: ...N SV PICS_SUBST Not Supported subVal ValWithTrans SV PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRING64 SV PICS_SUBST Not Supported Configuration Description and Extension persistent BOOLEAN CF M Not Supported ctlModel ENUMERATED CF Status only direct with normal security sbo with normal security direct with enhanced security sbo with enhanced security M Suppo...

Page 98: ...19 1 Binary controlled step position information BSC BSC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Control and Status ctlVal ENUMERATED CO stop lower higher reserved AC_CO_M Supported operTm TimeStamp CO AC_CO_O Not Supported origin Originator ST AC_CO_O Not Supported ct...

Page 99: ...T8 CF O Not Supported maxVal INT8 CF O Not Supported stepSize INT8U CF 1 maxVal minVal O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the control model ctlModel and connectivity packet sho...

Page 100: ...d subVal ValWithTrans SV PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRING 64 SV PICS_SUBST Not Supported Configuration Description and Extension ctlModel ENUMERATED CF Status only direct with normal security sbo with normal security direct with enhanced security sbo with enhanced security M Supported sboTimeout INT32U CF AC_CO_O Not Supported sboClass ENUMERAT...

Page 101: ...T qchg M Not Supported t TimeStamp ST M Not Supported Configuration Description and Extension ctlModel ENUMERATED CF direct with normal security M Not Supported units Unit CF see Annex A O Not Supported sVC ScaledValue Config CF AC_SCAV Not Supported minVal AnalogueValue CF O Not Supported maxVal AnalogueValue CF O Not Supported stepSize AnalogueValue CF 1 maxVal minVal O Not Supported d VISIBLE S...

Page 102: ...TRING255 EX AC_DLN_M Not Supported 11 2 2 23 Integer status setting ING Table 11 2 2 23 1 defines the common data class of integer status setting Table 11 2 2 23 1 Integer status setting ING APC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class see IEC 61850 7 2 Not Supported DataAttribute Setting setVal INT32 SP AC_NSG_M No...

Page 103: ... Not Supported DataAttribute Setting setMag AnalogueValue SP AC_NSG_M Not Supported setMag AnalogueValue SG SE AC_SG_M Not Supported Configuration Description and Extension units Unit CF see Annex A O Not Supported sVC ScaledValue Config CF AC_SCAV Not Supported minVal AnalogueValue CF O Not Supported maxVal AnalogueValue CF O Not Supported stepSize AnalogueValue CF 1 maxVal minVal O Not Supported...

Page 104: ...SG_O Not Supported setParD FLOAT32 SG SE AC_NSG_O Not Supported setParE FLOAT32 SG SE AC_NSG_O Not Supported setParF FLOAT32 SG SE AC_NSG_O Not Supported Configuration Description and Extension d VISIBLE STRING255 DC Text O Not Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 ...

Page 105: ...ame plate LPL Table 11 2 3 1 defines the common data class of logical node name plate Table 11 2 3 1 Logical node name plate LPL ASG class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Comments DataName Inherited from Data Class see IEC 61850 7 2 Supported DataAttribute Configuration Description and Extension vendor VISIBLE STRING255 DC M Supported hwRev VISIBLE STRING2...

Page 106: ... 11 2 3 1 1 defines the common data class of curve shape description Table 11 2 3 1 1 Curve shape description CSD CSD class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 400 Com ments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Suppor ted DataAttribute Configuration Description and Extension xUnit Unit DC M Not Suppor ted xD VISIBLE STRIN G255 DC M Not Sup...

Page 107: ...uppor ted 11 3 SCL conformance statement Table 11 3 1 defines the support of Substation Configuration Language Table 11 3 1 SCL conformance degrees SCL conformance Client CR Server CR Base F S Value Range Base F S SPA ZC 400 Comments SCL 1 SCL File for Implementa tion Available offline m m Supported CID file export SCL 2 SCL File available from implementa tion online O o o o Supported CID file can...

Page 108: ... O a o a Supported SetFile O b o b Supported DeleteFile O o o b Supported GetDataVa lues O c o c Not Supported SetDataVa lues O a o a Not Supported SCL Control Block I i o b Not Supported SCL File Structure I m i m Not Supported Remote Creation of SCL File I o i o Not Supported a Must be m if support for SCL 2 is declared b Must be m if support for SCL 3 is declared c Must be m if support for SCL ...

Page 109: ...11 4 1 Table 11 4 1 Definition of SCL control block IEC 61850 8 1Component Name MMS TypeDescription r w m o Comments SPA ZC 400 Comments validate VISIBLE STRING size of 64 octets rw mo Must be m if support for remote activation of an SCL is declared N A for TP client valState Unsigned Integer 8 bits r m 0 NOT VALIDATED 1 VALIDATION ERROR 2 VALIDATED 3 VALIDATION IN PROGRESS 4 NOT SUPPORTED 5 VALID...

Page 110: ... 400 Comments F S F S T1 TCP IP T Profile a a Supported T2 OSI T Profile b b Not Supported T3 GOOSE GSE T Profile c c Supported T4 GSSE T Profile d d Not Supported T5 TimeSync T Profile o o Supported a Must be m if support for A1 is declared Otherwise must be i b Must be o if support for A1 is declared Otherwise must be i c Must be m if support for A2 is declared Otherwise must be i d Must be m if...

Page 111: ... for either GetGoReference GetGOOSEElementNumber or GOOSE is declared Table 11 5 1 2 2 GSSE conformance Subscriber Publisher SPA ZC 400 Comments GSSE Services a a Not Supported SendGSSEEMessage M m Not Supported GetGsReference O b Not Supported GetGSSEDataOffset O b Not Supported GetGsCBValues O o Not Supported SetGsCBValues O o Not Supported GSENotSupported b o Not Supported GSSE Control Block Gs...

Page 112: ...112 ...

Page 113: ...113 12 KEMA certificate A060010 1MRS755347 Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 400 ...

Page 114: ...114 ...

Page 115: ...b site http www abb com substationautomation Select the appropriate product from the Distribution products drop down list and click OK Then select Download tab and from the Document kind drop down list select Software Finally click the Connectivity Package link to download it Table 13 1 Compatibility between IEC 61850 SPA ZC 400 CET Connectivity Packages and IEDs SPA ZC 40x version CET version Con...

Page 116: ...116 ...

Page 117: ...Logical Device Representation of a group of functions Each function is defined as a logical node A physical device has one or several LDs RJ 45 Galvanic connector type sAddr Short Address InformationThe sAddr attribute allows the allocation of a short address to DO attributes Short addresses can be used within the communica tion to be more efficient either in the communication or in the handling o...

Page 118: ...118 ...

Page 119: ...vice IP Internet Protocol LAN Local Area Network LD Logical Device LED Light Emitting Diode LN Logical Node LON Local Operating Network MMS Manufacturing Message Specification RCB Report Control Block SCADA Supervision Control and Data Acquisition SCL Substation Configuration Language defined by IEC 61850 SNTP Simple Network Time Protocol SPA Data communication protocol developed by ABB para SQL S...

Page 120: ......

Page 121: ......

Page 122: ...ABB Oy Distribution Automation P O Box 699 FI 65101 Vaasa FINLAND 358 10 2211 358 10 224 1080 www abb com substationautomation 1MRS755347 EN 6 2006 ...

Reviews: