background image

25

A060282

Fig. 5.4.1.-1

Connectivity Package Manager

5.4.2.

Uninstalling Connectivity Packages

1. Open the Add or Remove Programs dialog by selecting

Start > Settings >

Control Panel > Add or Remove Programs

.

2. Select the relevant Connectivity Package and click

Remove

.

5.5.

Connecting to SPA-ZC 402

The Sections 5.5.1. and 5.5.2. describe how to connect to SPA-ZC 402 from the
Communication Engineering Tool (CET) for SPA-ZC 40x.

5.5.1.

Changing computer's IP address

To connect SPA-ZC 402, the used computer and SPA-ZC 402 must use the same
address space.

To change the computer's IP address space to be the same as in SPA-ZC 402:

SPA/ Ethernet Adapter

SPA to IEC 61850 Gateway

Installation and Commissioning Manual

SPA-ZC 402

SPA-ZC 402

1MRS755380

Summary of Contents for SPA-ZC 402

Page 1: ...SPA Ethernet Adapter SPA ZC 402 SPA ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual ...

Page 2: ......

Page 3: ...r SPA ZC 40x 22 5 3 3 Uninstalling Communication Engineering Tool for SPA ZC 40x 23 5 4 Installing Connectivity Packages 23 5 4 1 Enabling Connectivity Packages 24 5 4 2 Uninstalling Connectivity Packages 25 5 5 Connecting to SPA ZC 402 25 5 5 1 Changing computer s IP address 25 5 5 2 Checking connection to SPA ZC 402 26 6 Engineering 29 6 1 Overview of engineering 29 6 2 Creating project 30 6 3 R...

Page 4: ...s 63 9 2 Communication settings 63 9 3 IP Query 64 9 4 Identification 65 9 5 Obtaining error logs 66 10 Troubleshooting 67 11 Technical reference 69 11 1 ACSI conformance statement 70 11 2 Model conformance statement 70 11 2 1 Common data attribute classes 70 11 2 1 1 Quality 71 11 2 1 2 Analogue value 72 11 2 1 3 Configuration of analogue value 72 11 2 1 4 Range configuration 72 11 2 1 5 Step pos...

Page 5: ...ion information BSC 91 11 2 2 20 Integer controlled step position information ISC 92 11 2 2 21 Controllable analogue set point information APC 94 11 2 2 22 Single point setting SPG 94 11 2 2 23 Integer status setting ING 95 11 2 2 24 Analogue setting ASG 96 11 2 2 25 Setting curve CURVE 96 11 2 2 26 Device name plate DPL 97 11 2 3 Logical node name plate LPL 98 11 2 3 1 Curve shape description CSD...

Page 6: ...6 ...

Page 7: ...eproduced or copied without written permission from ABB Oy and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose The software or hardware described in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Copyright 2009 ABB Oy All rights reserved Trademarks ABB is a registered ...

Page 8: ...8 ...

Page 9: ...ons or other important information The electrical warning icon indicates the presence of a hazard which could result in electrical shock The caution icon indicates important information or warning related to the concept discussed in the text It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property The information icon alerts the rea...

Page 10: ... MMS ISO 9506 1 and ISO 9506 2 and to ISO IEC 8802 3 Visit also the International Users Group UCA web page for more information about the IEC 61850 standard 1 5 Document conventions The following conventions are used for the presentation of material The words in names of screen elements for example the title in the title bar of a dialog the label for a field of a dialog box are initially capitaliz...

Page 11: ...ollowing message is displayed Entered value is not valid You may be told to enter the string MIF349 in a field The string is shown as follows in the procedure MIF349 Variables are shown using lowercase letters sequence name 1 6 Revision history Version Date History A 23 11 2004 Document created B 30 12 2004 Ordering information updated C 31 01 2005 Table 8 2 2 Surge immunity updated D 30 06 2006 S...

Page 12: ...12 ...

Page 13: ... electrical installation National and local electrical safety regulations must always be followed The device contains components which are sensitive to electrostatic discharge Unnecessary touching of electronic components must therefore be avoided SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 402 SPA ZC 402 1MRS755380 ...

Page 14: ...14 ...

Page 15: ...e by using Connectivity Package Manager see Fig 3 1 A060282 Fig 3 1 Connectivity Package Manager 3 Create a new project by selecting File Open Manage Project from CET for SPA ZC 40x 4 Install a new IEC 61850 device SPA ZC 40x by right clicking the project and selecting New IEC61850 SPA ZC 40x SPAZC40x_v1x is for the previous version SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Co...

Page 16: ...P Server 1 and 2 Subnet mask Refer to Section 5 5 1 Changing computer s IP address 8 Set Time Zone Correction 9 Rename the IED for example REF545_F1 10 Adjust IED SPA Communication parameters in the Object Properties panel 11 Adjust network adapter s IP address to same subnet as SPA ZC 402 To perform the operation open Windows XP Network Connections in Control Panel If CID file exists the IP addre...

Page 17: ...SPA ZC 402 The SPACOM 300 series rack is one SPA device The mechanical and electrical connection of the Ethernet adapter to an IED interface is described in Section 5 Installation The Ethernet adapter programming is described in Section 6 Engineering It is a prerequisite to understand the communication properties of Intelligent Electronic Devices IED before connecting to the Ethernet adapter This ...

Page 18: ...ands is routed through the IEC 61850 bus and the rest of the available data can be routed through SPA over TCP IP Only one SPA client can be configured to poll SPA events from the device By default SPA ZC 402 is configured to poll SPA events then it is not allowed to poll SPA events from another SPA client If the parallel IEC 61850 communication is configured for RE_ 541 3 5 with two SPA ZC 40x ga...

Page 19: ...answers to all requirements in substation The configuration of the protocol is flexible When using the IEC 61850 standard it is possible to allocate the functions and integrate the functionality freely The IEC 61850 standard supports the following functions Protection and control Integration of innovative sensor and switch technologies Metering supervisory control and data acquisition SCADA Remote...

Page 20: ...tomation the IEC 61850 standard defines data modeling and communication services for this specific domain Data modeling is mapped to a communication protocol Manufacturing Message Specification MMS ISO 9506 protocol which uses TCP IP and Ethernet In addition to the communication specifications engineering information exchange is defined in Substation Configuration Language SCL which is an XML base...

Page 21: ...ection Uaux is 110 220 VDC 100 240 VAC or 24 60 VDC Table 5 2 1 1 Screw terminal of Uaux connection Screw terminal AC DC 1 L 2 N In addition there is an earthing screw for the protective earth conductor beside the screw terminals in the casing 5 3 Communication Engineering Tool for SPA ZC 40x 5 3 1 System requirements Communication Engineering Tool CET for SPA ZC 40x runs on Windows 2000 Windows X...

Page 22: ...your local hard drive Click Next to continue the installation To install a manual click the respective manual and select Will be installed on local hard drive To install the documentation feature click the respective manual and select Entire feature will be installed on local hard drive To install the manual when required click the respective manual and select Feature will be installed when requir...

Page 23: ...the SPA ZC 402 configuration CD to the CD ROM drive of your PC The Connectivity Packages can be downloaded on the ABB web site http www abb com substationautomation Contact ABB to check the connectivity package s status for the Intelligent Electronic Device IED in question 2 Double click the Connectivity Package installation program and select the relevant IED msi to start the installation Install...

Page 24: ...a dialog which also shows the directory path where the files are copied to At this point you can still cancel the installation by clicking Cancel 9 A dialog opens to show that the Connectivity Package has been successfully installed Close the dialog and finish the installation by clicking Finish After installing a new CET for SPA ZC 40x version or new Connectivity Packages always activate the corr...

Page 25: ...Connecting to SPA ZC 402 The Sections 5 5 1 and 5 5 2 describe how to connect to SPA ZC 402 from the Communication Engineering Tool CET for SPA ZC 40x 5 5 1 Changing computer s IP address To connect SPA ZC 402 the used computer and SPA ZC 402 must use the same address space To change the computer s IP address space to be the same as in SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Insta...

Page 26: ...dministration rights to perform the task A060241 Fig 5 5 1 1 Changing IP address 5 5 2 Checking connection to SPA ZC 402 Check the connection to SPA ZC 402 by using the ping command 1 Open the Run dialog 2 Type cmd to the Open box see Fig 5 5 2 1 26 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755380 ...

Page 27: ...inging SPA ZC 402 SPA ZC 402responds to the ping command if the computer and SPA ZC 402 are on the same network 5 If SPA ZC 402 responds with the IP address the connection is established between the computer and SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 402 SPA ZC 402 1MRS755380 ...

Page 28: ...28 ...

Page 29: ...ructure consists of Logical devices LD Logical nodes LN Data objects DO Data attributes DA The data model is imported from the preconfigured object types of devices which have the objects defined and configured These object types are defined in the standardized IED Connectivity Packages The data model can also be created manually by using CET for SPA ZC 40x functions When the structure is complete...

Page 30: ... project A040014B Fig 6 2 2 Creating a new project 6 3 Restarting Use this function to restart the SPA ZC 402 at runtime 1 Select IED and Tools Restart SPAZC40x to open the restart panel see Fig 6 3 1 2 Click Reset The results are reported to the UI text box 30 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755380 ...

Page 31: ...object tree in the Communication Engineering Tool CET for SPA ZC 40x to define the communication structure Fig 6 4 1 shows an example of the object tree when it has been built In the example tree you can see the SPA ZC 402 object and its child objects as devices and data objects Indentation is used to indicate the parent child relationship between the objects SPA Ethernet Adapter SPA to IEC 61850 ...

Page 32: ...d a child object Use LN and DOI wizards to create new objects Add the objects in the following order 1 IEC 61850 Device object SPA ZC 40x 2 Logical Device objects 3 Logical Node objects 4 Data objects 5 Datasets 6 Reporting control blocks 7 GOOSE control blocks 8 GOOSE inputs 32 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755380 ...

Page 33: ... an IEC 61850 Device object Ensure that the new IED name is unique within the planned network by renaming the IED for example REF545_F1 A Tunneling Device object cannot be configured for an IEC 61850 gateway The Logical Device LD0 describes SPA ZC 402 and includes the data objects for diagnostics and description All data sets and report control blocks RCB are collected to LLN0 6 4 2 Adding Logical...

Page 34: ...ges A040154 Fig 6 4 2 1 Adding Logical Device objects The logical device object is now shown as a sub object to the IEC 61850 Device object see Fig 6 4 2 2 A040155 Fig 6 4 2 2 Logical node is shown as sub object You should have at least one Logical Device object as a child object to each IEC 61850 Device Object You can have a maximum of seven Logical Device objects under one Device Object LD0 and ...

Page 35: ...The functions which are not mapped to the IEC 61850 structure are reported after import The tool imports default data sets and report control blocks RCB to logical device LD0 see Fig 6 4 3 1 Data sets include a set of selected data attributes from IED s IEC 61850 data model These data sets are used in the IEC 61850 event reporting model If data attributes are selected to the data set and the same ...

Page 36: ...aset is too long You can modify dataset by using Dataset Editor Open Dataset Editor by selecting the dataset and right click to open Dataset Editor Dataset has a set of data attributes logical device instance name optional prefix logical node instance name logical node class data object name and functional constraint FC Functional constraint divides data attributes to groups which have the same fu...

Page 37: ... which referenced dataset belongs Prefix Freely configurable part of LN Caption InInst Instance of the LN type Class of the LN type InClass doName Name of the data object from which dataset is formed daName Name of the data attribute from which dataset is formed from fc Identifies the signal measurement type to MX if the status is ST Prefix InClass and InInst define the object tree s caption Capti...

Page 38: ...re IP Address IP address identifies SPA ZC 402 in Local Area Network LAN All communication via SPA ZC 402 uses this address The default value is 192 168 2 10 and it has to be changed to a unique address according to the planned network structure Default Gateway This IP address defines the gateway s address which forwards IP traffic between the local subnet and outside world The default value is 19...

Page 39: ... client uses these addresses to access SPA ZC 402 over MMS An established IEC61850 connection uses the TCP keepalive functionality if there is no other active communication ongoing TCP keepalive is sent every 15 seconds If the peer is not responding it is considered to be time outed and the TCP connection is closed Fig 6 7 1 General communication parameters 6 7 1 SPA Communication parameters SPA A...

Page 40: ...is defined in the IEC 61850 8 1 standard and SPA ZC 402 is also synchronizing IED over SPA Disabled In this mode you can only synchronize SPA ZC 402 with SNTP and IED has a different source of time synchronization Read from device if supported When this operation mode is selected the time for SPA ZC 402 is read from IED over SPA SNTP is not in use and the IED gets time synchronization from another...

Page 41: ...3 5 and REX 521 A040022 Fig 6 7 1 1 SPA Communication Parameters Locally SPA ZC 402 uses UTC Coordinated Universal Time time which is received from the SNTP time synchronization by default This time format does not use Daylight Saving Time If you want that the IED and SPA communication uses this time format the IEC 61850 client has to be programmed to write the minute offset of the UTC time to the...

Page 42: ...e old IP address from the previous configuration The IP addresses can be verified with for example IP Query Tool For more information about IP Query Tool refer to Section 9 3 IP Query A040029B Fig 6 8 1 Downloading the device s configuration You can export a configuration in CID format from CID Export tool to hard drive This SCL is usually used by System Configuration tool It is possible to export...

Page 43: ...g Logical Device objects The IEC 61850 standard defines a mandatory logical node LLN0 for every device and its objects For best practice check some ready projects based on Connectivity Packages Adding and configuring logical nodes manually contains four main steps 1 Add a logical node for example CILO for the circuit breaker objects with the LN Wizard see Fig 6 9 1 2 Add data objects 3 Configure t...

Page 44: ... start the DO Wizard see Fig 6 9 2 7 Select the DOType Depending on the DOType selected corresponding data attributes are automatically added 8 Type the DOI name 9 Click Add DOI button for every data object you add 44 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS755380 ...

Page 45: ...n about data objects refer to Section 11 2 Model conformance statement 11 Define properties to the data objects In order to map the added IEC 61850 data objects to the SPA data model you have to define the properties for each data object 12 Right click the data object to select Properties from the shortcut menu to activate the Object Properties window SPA Ethernet Adapter SPA to IEC 61850 Gateway ...

Page 46: ... same procedure for all data objects that you have added to the LN object A040133B Fig 6 9 3 Data Object Instance Editor The SPA point data is written to the sAddr in the CID file for the selected data object SPA ZC 402 uses this field to poll data and events from the IED In order to get automatic updating of the process objects you should add those data objects of interest to the dataset group Re...

Page 47: ...e first change before sending the report Value 0 means that a new change is immediately reported to the client without waiting for any additional changes In practice the buffer time can be from 0 to a few seconds without a notable effect on the client s event notification delays The default values are suitable in most cases Dataset The Dataset property defines the data set to be sent as time tagge...

Page 48: ...ax property Defines how many clients are using this RCB that is the number of needed RCB instances If you define two clients for buffered reporting Max has to be 2 SPA ZC 402 creates two instances of RCB name for example rcbStatNrml01 and rcbStatNrml02 For unbuffered reporting Max has to be same as the number of defined clients or higher This is defined in the IEC 61850 standard Trigger Options Da...

Page 49: ...s not mandatory to define clients in unbuffered reporting but it is recommended for the sake of clarity Client IED Name has to match with the client name in Substation Configuration description Language SCL Every modification in the Dataset referenced in RCB increases the RCB Configuration Revision property by one The IEC 61850 client can verify the deviations between the received configuration re...

Page 50: ...ctivity Package or the CID file is imported the Scales object is created automatically 2 Right click Scales in the Project Explorer pane and select New Scales see Fig 6 11 1 A060131 Fig 6 11 1 Adding a new scale 3 Select the Scales type Look up Table or Stepwise Linear 4 Configure the selected scale s properties see Fig 6 11 2 50 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway ...

Page 51: ...6 11 2 Configuring properties 5 Create reference to scale at DO level in object tree see Fig 6 11 3 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 402 SPA ZC 402 1MRS755380 ...

Page 52: ...ad the recorded data and convert it to standard COMTRADE files in year 1999 format The conversion is done automatically and the Disturbance Recorder Ready signal is sent to IEC 61850 client after new files are ready to be read A relay with compatible MEDREC16 function block notifies SPA ZC 402 when it has new recordings ready SPA ZC 402 reads the actual data from the relay as a background process ...

Page 53: ...4 cfg Configuration file yymmddnn dat 70010104 dat Data file yymmddnn inf 70010104 inf Information file The filename consists of the following parts Part Format Description yy 00 99 Record creation timestamp year mm 01 12 Record creation timestamp month dd 01 31 Record creation timestamp date nn 00 99 Running serial number of the records of the same day The Configuration Data and Information files...

Page 54: ...54 ...

Page 55: ...f SPA ZC 402 from the data model LD0 LLN0 Health stVal 1 OK configuration is completed successfully 2 Warning no clock synchronization 3 Alarm connection to the IED could not be established or errors appear during the data model configuration If the configuration fails check the error log files from the SPA ZC 402 file system The status and error logs are located in the log directory For more info...

Page 56: ...cessfully you can check the resettable diagnostic counters through the IEC 61850 data model SPA ZC 402 Diagnostic counters are part of the LD0 CDGGIO1 logical node The data object type is ABB specific extension in IEC 61850 data model and contains the counters as data attributes It is possible to reset the counters by writing 1 into ctlVal It is not recommended to put the counters into the data se...

Page 57: ...lity value is GOOD If this is not the case configurations between SPA ZC 402 and IED are not identical If all the data objects have INVALID quality the SPA communication is not running SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 402 SPA ZC 402 1MRS755380 ...

Page 58: ...58 ...

Page 59: ...connector Optical fibres See fibre optic guides SPA ZF Optical glass fibres multimode graded index type Plastic core fibre optic cables features and instructions for mounting For more information see Section 1 4 Product documentation Diagnostic LEDs SPA ZC 402 common diagnostic LEDs Power Diagnostic Red Green Yellow LAN diagnostic LEDs LINK TX RX SPA diagnostic LEDs TX RX SPA Ethernet Adapter SPA ...

Page 60: ...ET LAN IEC 61850 SPA TCP MODBUS TCP A040027B Fig 8 1 1 Dimensions of the SPA ZC 402 module Table 8 1 1 Dimensions and weight Type Dimensions mm Weight g SPA ZC 402 190 x 115 x 35 510 8 2 Test and conditions SPA ZC 402 fulfills IEC 61850 3 Communication networks and systems in substations 60 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1M...

Page 61: ...g to the IEC 61000 4 6 and IEC 60255 22 6 10 V rms f 150 kHz 80 MHz Radiated amplitude modulated According to the IEC 61000 4 3 and IEC 60255 22 3 10 V m rms f 80 2700 MHz Radiated pulse modulated According to the ENV 50204 and IEC 60255 22 3 10 V m f 900 MHz Fast transient disturbance tests According to the IEC 60255 22 4 and IEC 61000 4 4 All terminals 4 kV Surge immunity test According to the I...

Page 62: ...xC Input voltage AC 110 120 220 240 V Input voltage DC 110 125 220 V 24 48 64 V Voltage variation AC 85 110 DC 80 120 of rated value DC 80 120 of rated value Burden 4 W Ripple in DC auxiliary voltage Max 12 of the rated DC value IEC 60255 11 Interruption time in auxiliary DC voltage without resetting 110 V 40 ms 24 V 24 ms 62 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Inst...

Page 63: ...f Flashing 1 2 3 4 5 6 Bootloader booting Bootloader missing boot image Starting OK missing configuration OK configuration in use Configuration error Possible sequences are 1 3 5 Normal situation 1 2 Missing boot image 1 3 4 Configuration file is missing 1 3 6 Configuration error If configuration error is detected because of the mismatches in downloaded the CID file download a simpler configuratio...

Page 64: ...mple Sending IP query 1 RECEIVED MESSAGE FROM 10 58 125 151 Mac Address 00 0C 02 B0 04 89 Subnet Mask 255 255 255 0 Default Gateway 10 58 125 150 SNTP servers 10 58 125 150 127 0 0 1 SW_SPATYPE SPA ZC40x SW_NUMBER 1MRS118533 SW_BUILD 110 SW_REVISION B Compiler DATE_TIME Nov 28 2005 12 38 02 To use the IP Query Tool 1 Select Tools IP Query Tool to start the tool see Fig 9 3 1 Query activates device...

Page 65: ... version 2 0 is used MAC address other address and revision information is displayed 9 4 Identification If contacting the Customer Service it is necessary to send the following information by request Version of Connectivity Packages The version can be checked from the Connectivity Package Manager Version information of Communication Engineering Tool CET for SPA ZC 40x SPA Ethernet Adapter SPA to I...

Page 66: ...et the correct version information from the device memory For more information about IP query refer to Section 9 3 IP Query 9 5 Obtaining error logs The following session transfers error log file through ftp C ftp x x x x User abb Password abb ftp cd log ftp get error log ftp quit 66 SPA ZC 402 SPA ZC 402 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual 1MRS75538...

Page 67: ...EC 61850 communication protocol port 102 Network time management protocol port 123 Modbus TCP port 502 A firewall may prevent the FTP and IP Query to work In case of problems adjust the firewall settings so that the ports listed in Table 10 1 are open IP Query uses the broadcast address 255 255 255 255 to which the query is sent and which may also be blocked Windows XP SP 2 contains a built in fir...

Page 68: ...68 ...

Page 69: ...ntation conformance statement The conformance statements and documents are referred to as Protocol Implementation Conformance Statement PICS and Model Implementation Conformance Statement MICS For the following clauses the following definitions apply Table 11 1 Notations M m Mandatory support The item must be implemented C c Conditional support The item must be implemented if the stated condition ...

Page 70: ...ber side O Supported Transmission of sampled value model SVC B41 Publisher side O Not Supported B42 Subscriber side O Not Supported 11 2 Model conformance statement In this chapter the Model Implementation Conformance Statement MICS is defined detailing the standard data object model elements supported by SPA ZC 402 It is also possible to export the information in MICS to a CID file The CID file c...

Page 71: ...EAN M Defaulted oldData BOOLEAN M Supported inconsistent BOOLEAN M Defaulted inaccurate BOOLEAN M Defaulted source CODED ENUM process substituted DEFAULT process M Supported test BOOLEAN DEFAULT FALSE M Defaulted operatorBlocked BOOLEAN DEFAULT FALSE M Defaulted The DEFAULT value must be applied if the functionality of the related attribute is Not Supported The mapping may specify to exclude the a...

Page 72: ... configuration Table 11 2 1 4 1 Range configuration RangeConfig Type Definition Attribute Name AttributeType Value Value Range M O C SPA ZC 402 Comments hhLim AnalogueValue M Supported hLim AnalogueValue M Supported ILim AnalogueValue M Supported IILim AnalogueValue M Supported min AnalogueValue M Supported max AnalogueValue M Supported 11 2 1 5 Step position with transient indication Table 11 2 1...

Page 73: ...he substation e g network control center automatic bay Control operation issued from an automatic function at bay level automatic station Control operation issued from an automatic function at station level automatic remote Control operation issued from an automatic function outside of the substation maintenance Control operation issued from a maintenance service tool process Status change occurre...

Page 74: ...ue Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Status stVal BOOLEAN ST dchg TRUE FALSE M Supported q Quality ST qchg M Supported t TimeStamp ST M Supported Substitution subEna BOOLEAN SV PICS_SUBST Not Supported subVal BOOLEAN SV TRUE FALSE PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STR...

Page 75: ...bID VISIBLE STRING64 SV PICS_SUBST Not Supported Configuration Description and extension d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported 11 2 2 3 Integer status INS Table 11 2 2 3 1 defines the common data class of integer status Table 11 2 2 3 1 In...

Page 76: ...able 11 2 2 4 1 Protection activation information ACT ACT class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Status general BOOLEAN ST dchg M Supported phsA BOOLEAN ST dchg O Supported phsB BOOLEAN ST dchg O Supported phsC BOOLEAN ST dchg O Supported neut BOOLEAN ST dchg O Suppor...

Page 77: ... Supported DataAttribute Status general BOOLEAN ST dchg M Supported dirGeneral ENUMERATED ST dchg unknown forward backward both M Supported PhsA BOOLEAN ST dchg GC_2 1 Supported dirPhsA ENUMERATED ST dchg unknown forward backward GC_2 1 Supported PhsB BOOLEAN ST dchg GC_2 2 Supported dirPhsB ENUMERATED ST dchg unknown forward backward GC_2 2 Supported PhsC BOOLEAN ST dchg GC_2 3 Supported dirPhsC ...

Page 78: ... SEC SEC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Status cnt INT32U ST dchg M Not Supported sev ENUMERATED ST unknown critical major minor warning M Not Supported T TimeStamp ST M Not Supported addr OCTET STRING64 ST O Not Supported addInfo VISIBLE STRING64 ST O Not...

Page 79: ... CF GC_2 1 Not Supported strTm TimeStamp CF GC_2 1 Not Supported frPd INT32 CF GC_2 1 Not Supported frRds BOOLEAN CF GC_2 1 Not Supported d VISIBLE STRING255 DC O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 8 Measured value MV Table 11 2 2 8 1 defines the common data cl...

Page 80: ...zeroDb INT32U CF 0 100 000 O Not Supported sVC ScaledValue Config CF AC_SCAV Not Supported rangeC RangeConfig CF GC_CON Not Supported smpRate INT32U CF O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exis...

Page 81: ...ration Description and Extension units Unit CF see Annex A O Supported db INT32U CF 0 100 000 O Not Supported zeroDb INT32U CF 0 100 000 O Not Supported rangeC RangeConfig CF GC_CON Supported magSVC ScaledValue Config AC_SCAV Not Supported angSVC ScaledValue Config AC_SCAV Not Supported angRef ENUMERATED CF V A other O Not Supported smpRate INT32U CF O Not Supported d VISIBLE STRING255 DC Text O S...

Page 82: ...ported DataAttribute Configuration Description and Extension angRef ENUMERATED CF Va Vb Vc Aa Ab Ac Vab Vbc Vca Vother Aother O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the CMV type va...

Page 83: ...AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the CMV type variant 11 2 2 12 Sequence SEQ Table 11 2 2 12 1 defines the common data class of sequence Table 11 2 2 12 1 Sequence SEQ SAV class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61...

Page 84: ...Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Measured Values Basics q Quality MX qchg M Not Supported t TimeStamp MX M Not Supported Harmonics and Interharmonics har ARRAY 0 numHar OF Vector MMX dchg dupd M Not Supported Configuration Description and Extension numHar INT16U CF 1 M Not Supported numCycl INT16U CF 0 M Not Supported evalTim INT16U CF M Not Supported units Unit CF see...

Page 85: ...2 14 1 Harmonic value for WYE HWYE HWYE class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Not Supported DataAttribute Measured Values Basics q Quality MX qchg M Not Supported t TimeStamp MX M Not Supported Harmonics and Interharmonics phsAHar ARRAY 0 numHar OF Vector MX dchg dupd M Not Supported phsBHa...

Page 86: ...RING255 DC Text O Not Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 15 Harmonic value for DEL HDEL Table 11 2 2 15 1 below defines the common data class of harmonic value for DEL Table 11 2 2 15 1 Harmonic value for DEL HDEL HDEL class Attribute Name Attribute Type FC Trg...

Page 87: ...Not Supported d VISIBLE STRING255 DC Text O Not Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 16 Controllable single point SPC Table 11 2 2 16 1 defines the common data class of controllable single point Table 11 2 2 16 1 Controllable single point SPC SPC class Attribute ...

Page 88: ...curity sbo with normal security direct with enhanced security sbo with enhanced security M Supported sboTimeout INT32U CF AC_CO_O Not Supported sboClass ENUMERATED CF operate once operate many AC_CO_O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M No...

Page 89: ...al CODED ENUM SV intermediate state off on bad state PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRING64 SV PICS_SUBST Not Supported Configuration Description and Extension pulseConfig PulseConfig CF AC_CO_O Not Supported ctlModel ENUMERATED CF status only direct with normal security sbo with normal security direct with enhanced security sbo with enhanced secur...

Page 90: ...255 AC_CO_O Not Supported stVal INT32 ST dchg M Supported q Quality ST qchg M Supported t TimeStamp ST M Supported stSeld BOOLEAN ST dchg AC_CO_O Not Supported Substitution subEna BOOLEAN SV PICS_SUBST Not Supported subVal ValWithTrans SV PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRING64 SV PICS_SUBST Not Supported Configuration Description and Extension pers...

Page 91: ... controlled step position information Table 11 2 2 19 1 Binary controlled step position information BSC BSC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported DataAttribute Control and Status ctlVal ENUMERATED CO stop lower higher reserved AC_CO_M Supported operTm TimeStamp CO AC_CO_O Not Supp...

Page 92: ...axVal INT8 CF O Not Supported stepSize INT8U CF 1 maxVal minVal O Not Supported d VISIBLE STRING255 DC Text O Supported cdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported Different variants of the type exist based on the control model ctlModel and connectivity packet short address information ...

Page 93: ...bVal ValWithTrans SV PICS_SUBST Not Supported subQ Quality SV PICS_SUBST Not Supported subID VISIBLE STRING 64 SV PICS_SUBST Not Supported Configuration Description and Extension ctlModel ENUMERATED CF Status only direct with normal security sbo with normal security direct with enhanced security sbo with enhanced security M Supported sboTimeout INT32U CF AC_CO_O Not Supported sboClass ENUMERATED C...

Page 94: ...t Supported t TimeStamp ST M Not Supported Configuration Description and Extension ctlModel ENUMERATED CF direct with normal security M Not Supported units Unit CF see Annex A O Not Supported sVC ScaledValue Config CF AC_SCAV Not Supported minVal AnalogueValue CF O Not Supported maxVal AnalogueValue CF O Not Supported stepSize AnalogueValue CF 1 maxVal minVal O Not Supported d VISIBLE STRING255 DC...

Page 95: ... 2 23 1 defines the common data class of integer status setting Table 11 2 2 23 1 Integer status setting ING APC class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class see IEC 61850 7 2 Not Supported DataAttribute Setting setVal INT32 SP AC_NSG_M Not Supported setVal INT32 SG SE AC_SG_M Not Supported Configuration Description and...

Page 96: ...SIBLE STRING255 DC Text O Not Supported CdcNs VISIBLE STRING255 EX AC_DLNDA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 25 Setting curve CURVE Table 11 2 2 25 1 defines the common data class of setting curve Table 11 2 2 25 1 Setting curve CURVE ASG class Attribute Name Attribute Type FC TrgOp Value Value range M O...

Page 97: ...SIBLE STRING255 EX AC_DLNDA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 2 2 26 Device name plate DPL Table 11 2 2 26 1 defines the common data class of device name plate Table 11 2 2 26 1 Device name plate DPL ASG class Attribute Name Attribute Type FC TrgOp Value Value range M O C SPA ZC 402 Comments DataName Inherited from Data Class refer to IEC 61850 7 2 Supported Dat...

Page 98: ...ass see IEC 61850 7 2 Supported DataAttribute Configuration Description and Extension vendor VISIBLE STRING255 DC M Supported hwRev VISIBLE STRING255 DC M Supported d VISIBLE STRING255 DC Text M Supported configRev VISIBLE STRING255 DC AC_LN0_M Supported ldNs VISIBLE STRING255 EX must be included only in LLN0 AC_LN0_M Supported lnNs VISIBLE STRING255 EX AC_DLD_M Supported cdcNs VISIBLE STRING255 E...

Page 99: ... Supported yUnit Unit DC M Not Supported yD VISIBLE STRING255 DC M Not Supported numPts INT16U DC M Not Supported crvPts ARRAY 1 numPt OF M Not Supported xVal FLOAT32 DC xVal FLOAT32 DC d VISIBLE STRING255 DC M Not Supported cdcNs VISIBLE STRING255 EX AC_DLN DA_M Not Supported cdcName VISIBLE STRING255 EX AC_DLN DA_M Not Supported dataNs VISIBLE STRING255 EX AC_DLN_M Not Supported 11 3 SCL conform...

Page 100: ...ort the ACSI services defined in Table 11 3 2 Table 11 3 2 Supported ACSI services for SCL 2 and SCL 3 SCL conformance Client CR Server CR Base F S Value Range Base F S SPA ZC 402 Comments ACSI Services Not Supported GetFileAttribu teValues O o o m Supported GetFile O a o a Supported SetFile O b o b Supported DeleteFile O o o b Supported GetDataVa lues O c o c Not Supported SetDataVa lues O a o a ...

Page 101: ...ts defined in Table 11 4 1 Table 11 4 1 Definition of SCL control block IEC 61850 8 1Component Name MMS TypeDescription r w m o Comments SPA ZC 402 Comments validate VISIBLE STRING size of 64 octets rw mo Must be m if support for remote activation of an SCL is declared N A for TP client valState Unsigned Integer 8 bits r m 0 NOT VALIDATED 1 VALIDATION ERROR 2 VALIDATED 3 VALIDATION IN PROGRESS 4 N...

Page 102: ...I T Profile b b Not Supported T3 GOOSE GSE T Profile c c Supported T4 GSSE T Profile d d Not Supported T5 TimeSync T Profile o o Supported a Must be m if support for A1 is declared Otherwise must be i b Must be o if support for A1 is declared Otherwise must be i c Must be m if support for A2 is declared Otherwise must be i d Must be m if support for A3 is declared Otherwise must be i 11 5 1 1 MMS ...

Page 103: ... 2 2 GSSE conformance Subscriber Publisher SPA ZC 402 Comments GSSE Services a a Not Supported SendGSSEEMessage M m Not Supported GetGsReference O b Not Supported GetGSSEDataOffset O b Not Supported GetGsCBValues O o Not Supported SetGsCBValues O o Not Supported GSENotSupported b o Not Supported GSSE Control Block GsCB O o Not Supported a Must be m if support is declared within ACSI basic conforma...

Page 104: ...104 ...

Page 105: ...105 12 KEMA certificate A060010 SPA Ethernet Adapter SPA to IEC 61850 Gateway Installation and Commissioning Manual SPA ZC 402 SPA ZC 402 1MRS755380 ...

Page 106: ...106 ...

Page 107: ...ion Select the appropriate product from the Distribution products drop down list and click OK Then select Download tab and from the Document kind drop down list select Software Finally click the Connectivity Package link to download it Table 13 1 Compatibility between IEC 61850 SPA ZC 402 CET Connectivity Packages and IEDs SPA ZC 40x version CET version Connectivity Package versions devices and re...

Page 108: ...108 ...

Page 109: ...vice Representation of a group of functions Each function is defined as a logical node A physical device has one or several LDs RJ 45 Galvanic connector type sAddr Short Address InformationThe sAddr attribute allows the allocation of a short address to DO attributes Short addresses can be used within the communication to be more efficient either in the communication or in the handling of messages ...

Page 110: ...110 ...

Page 111: ...gical device LED Light emitting diode LN Logical node MICS Model implementation conformance statement MMS Manufacturing message specification MV Medium voltage OSI Open System Interconnection PC Personal computer PICS Protocol implementation conformance statement RCB Report Control Block SCADA Supervision control and data acquisition SCL Substation configuration description language defined by IEC...

Page 112: ...ABB Oy Distribution Automation P O Box 699 FI 65101 Vaasa FINLAND 358 10 2211 358 10 224 1080 www abb com substationautomation 1MRS755380 EN 5 2009 ...

Reviews: