33
6.4.1.
Adding Device object
To build the object tree:
1. Add an IEC 61850 Device object in the communication structure by selecting the
project name.
2. Right-click Protocol Test
3. Select
New > IEC 61850 > SPAZC40x_v2x
, see Fig. 6.4.1.-1.
Normally, the SPAZC40x_v2x template from the menu is used. Only if the
connected SPA-ZC 402 is an older version 1.1.1, you have to select its own IED
template SPAZC40x_v1x from the menu. This is illustrated in the following figure.
A project can contain several IEC 61850 device objects, for example all substation
feeder configurations and exported communication must be done separately for each
device.
A040023_3
Fig. 6.4.1.-1
Adding an IEC 61850 Device object
Ensure that the new IED name is unique within the planned network by renaming
the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC 61850
gateway.
The Logical Device LD0 describes SPA-ZC 402 and includes the data objects for
diagnostics and description. All data sets and report control blocks (RCB) are
collected to LLN0.
6.4.2.
Adding Logical Device objects
Communication Engineering Tool (CET) creates logical device LD0 automatically
for SPA-ZC 402 when creating a new IED. All datasets and reporting control blocks
(RCB) are grouped under LD0 for event handling. It has also basic logical nodes
and data objects for diagnostics and device information.
Do not change the name of the LD0.
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
SPA-ZC 402
SPA-ZC 402
1MRS755380
Summary of Contents for SPA-ZC 402
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 14: ...14 ...
Page 28: ...28 ...
Page 54: ...54 ...
Page 58: ...58 ...
Page 68: ...68 ...
Page 104: ...104 ...
Page 106: ...106 ...
Page 108: ...108 ...
Page 110: ...110 ...