13
Settings
The settings of the module can be entered either
via the push-buttons and the display on the
front panel or over the serial communication
system. The setting values are indicated by the
three digits to the right on the display. The LED
indicators in front of the setting value symbols
on the front panel indicate the group of settings
or the setting value displayed at a given moment.
Manual setting of the module is described in
"Main menu and submenus of settings and
registers".
Setting
Description
Setting range
(Default value)
Shot 1
Selection of operation mode for signals AR1...3:
AR1 (the third digit from the right)
0...2
AR2( the second digit from the right)
0...2
AR3 (the right-most digit)
0...2
(000)
0 = no operation
1 = Initiation of AR shot 1 (Start)
2 = Initiation of AR shot 1 inhibited (Block)
1st submenu:
Selection of the operation mode for signal AR4
0...2
(the right-most digit):
(--0)
0 = no operation
1 = Initiation of AR shot 1 (Start)
2 = Blocking of AR shot 1 (Block)
2nd submenu:
Dead time of AR shot 1
0.2...300 s (5 s)
Start delay time
3rd submenu:
- for initiation signal AR1
0...10 s (0 s)
4th submenu:
- for initiation signal AR2
0...10 s (0 s)
5th submenu:
- for initiation signal AR3
0...10 s (0 s)
6th submenu:
- for initiation signal AR4
0...10 s (0 s)
Shot 2
See shot 1
Shot 3
See shot 1
Shot 4
See shot 1
Shot 5
See shot 1