24
Technical data
Maximum number of successive AR shots
during a sequence
5
Start delay
0.00...10.0 s
Dead time
0.20...300 s
Discriminating time
0.00...30.0 s
Reclaim time
0.20...300 s
Final trip time
0.00...5.00 s
CB closing impulse
0.10...2.00 s
CB opening impulse
0.10...2.00 s
Operate time accuracy
±
1% of setting value or
±
30 ms
Event codes
Connected to a data communicator over the
SPA bus, the auto-reclose module generates
events which can be printed out, for instance, on
a printer. The events are printed in the format:
time, text, event code. The event text is written
by the user.
Most of the events can be included in or ex-
cluded from reporting by writing an event mask
(V155...V158) to the module. The parameters
of the event mask are presented in the tables
below.
The event codes E50...E54 and the events rep-
resented by these cannot be excluded from event
reporting.
Maximum 60 events can be stored in the event
buffer. When the 61st event message is received
the code E51 will be stored in the buffer. The
buffer and the code E51 are reset by giving the
parameter WC the value 0.
The event codes E52...E54 are generated by a
higher-level data communicator unit (e.g. SACO
100M, SRIO 1000M, etc.)
Detailed information about the serial commu-
nication over the SPA bus is given in the docu-
ment "SPA Bus Communication Protocol" 34
SPACOM 2EN1.
Channel Code
Event
Weighting Default
coefficient
General events
0
E1
AR (shots 1...5) started
1
1
0
E2
AR (shots 1...5) initiated by AR1
2
0
0
E3
AR (shots 1...5) initiated by AR2
4
0
0
E4
AR (shots 1...5) initiated by AR3
8
0
0
E5
AR (shots 1...5) initiated by AR4
16
0
0
E6
AR (shots 1...5) ended
32
1
0
E7
AR sequence successful
64
0
0
E8
AR sequence initiated by AR1 successful
128
0
0
E9
AR sequence initiated by AR2 successful
256
0
0
E10
AR sequence initiated by AR1 successful
512
0
0
E11
AR sequence initiated by AR1 successful
1024
0
0
E50
Restart of module
*
-
0
E51
Overflow of event register
*
-
0
E52
Temporary disturbance in data communication
*
-
0
E53
No response from the module over the data comm.
*
-
0
E54
The module responds again over the data comm.
*
-
Event mask
V155 = 33
Summary of Contents for SPAA 341 C /E351