29
Data
Channel Code
Data
Value
direction
Setting parameters
Setting values for AR shot 1 on channel 1, for AR shot 2 on channel 2, etc.
Dead time, AR shots 1...5
1...5
S1
R,W,(P)
0.2...300 s
Initiated by signal AR1
1...5
S2
R,W,(P)
0 = no operation
1 = AR shot initiated
2 = initiation of AR shot
blocked
Initiated by signal AR2
1...5
S3
R,W,(P)
0 = no operation
1 = AR shot initiated
2 = initiation of AR shot
blocked
Initiated by signal AR3
1...5
S4
R,W,(P)
0 = no operation
1 = AR shot initiated
2 = initiation of AR shot
blocked.
Initiated by signal AR4
1...5
S5
R,W,(P)
0 = no operation
1 = AR shot initiated
2 = initiation of AR shot
blocked.
Start delay when AR shot initiated by
- signal AR1
1...5
S6
R,W,(P)
0...10 s
- signal AR2
1...5
S7
R,W,(P)
0...10 s
- signal AR3
1...5
S8
R,W,(P)
0...10 s
- signal AR4
1...5
S9
R,W,(P)
0...10 s
Discriminating time t
d
1...4
S10
R,W,(P)
0...30 s
Final trip on channel 6
Final trip initiated by
- signal AR1
6
S2
R,W,(P)
1 = final trip by signal AR1
- signal AR2
6
S3
R,W,(P)
1 = final trip by signal AR2
- signal AR3
6
S4
R,W,(P)
1 = final trip by signal AR3
- signal AR4
6
S5
R,W,(P)
1 = final trip by signal AR4
Final trip time, when initiated by
- signal AR1
6
S6
R,W,(P)
0...5.0 s
- signal AR2
6
S7
R,W,(P)
0...5.0 s
- signal AR3
6
S8
R,W,(P)
0...5.0 s
- signal AR4
6
S9
R,W,(P)
0...5.0 s
Summary of Contents for SPAA 341 C /E351
Page 130: ......