12
Switch
Function
Factory
default
SGF4/1
Selection of self-holding for output signal TS1
0
SGF4/2
Selection of self-holding for output signal TS2
0
SGF4/3
Selection of self-holding for output signal TS3
0
SGF4/4
Selection of self-holding for output signal TS4
0
When the switch is in position 0, the output signal returns to its
initial state, when the measuring signal that caused operation falls
below the set start level.
When the switch is in position 1 the output signal remains high
although the measuring signal that caused operation falls below
the set start level.
At self-holding the output signal is reset with the push-buttons on the
front panel, via an external control input or the serial bus, see section
"Description of function".
SGF4/5
Starting of the circuit breaker failure protection (CBFP) by signal TS2
0
SGF4/6
Starting of the circuit breaker failure protection (CBFP) by signal TS3
0
SGF4/7
Starting of the circuit breaker failure protection (CBFP) by signal TS4
0
When the switch is in position 1, the output signal TS_ starts the
circuit breaker failure protection. If the operate time of the CBFP
expires while the output signal is active, the CBFP generates an
operate signal TS1.
When the switch is in position 0, the CBFP is set out of use.
SGF4/8
Not in use
0
∑
SGF4
0
SGF5/1
Selection of the signal to control the TRIP indicator on the front panel.
0
SGF5/2
When the switch corresponding to a certain output signal is in
1
SGF5/3
position 1, the TRIP indicator is lit on activation of the output signal.
0
SGF5/4
1
SGF5/5
Switch
Output signal
Switch position
0
SGF5/6
TRIP indicator
TRIP indicator lit
1
SGF5/7
not lit
0
SGF5/8
1
SGF5/1
SS1
0
1
SGF5/2
TS1
0
1
SGF5/3
SS2
0
1
SGF5/4
TS2
0
1
SGF5/5
SS3
0
1
SGF5/6
TS3
0
1
SGF5/7
SS4
0
1
SGF5/8
TS4
0
1
∑
SGF5
170