7
Table 2. Matching of the power transformer
vector group, when the HV side of the power
transformer is delta connected.
0
0
0
0
0
0
0
Dd6
Dd0
Yy0
Yy0
1
0
0
0
0
0
1
Dy7
Dy1
Yd1
Yy0
0
1
0
0
0
0
2
Dy11
Dy5
Yd5
Yy0
1
1
0
0
0
0
3
Dd0
Dd6
Yy6
Yy0
0
0
1
0
0
0
4
Dy1
Dy7
Yd7
Yy0
1
0
1
0
0
0
5
Dy5
Dy11
Yd11
Yy0
0
1
1
0
0
0
6
Dyn5
Dyn11
Yy0
Yd1
1
1
1
0
0
0
7
Dd6
Dd0
Yd1
Yd1
0
0
0
1
0
0
8
Dd10
Dd4
Yd5
Yd1
1
0
0
1
0
0
9
Dyn11
Dyn5
Yy6
Yd1
0
1
0
1
0
0
10
Dd0
Dd6
Yd7
Yd1
1
1
0
1
0
0
11
Dd4
Dd10
Yd11
Yd1
0
0
1
1
0
0
12
Dyn1
Dyn7
Yy0
Yd5
1
0
1
1
0
0
13
Dd2
Dd8
Yd1
Yd5
0
1
1
1
0
0
14
Dd6
Dd0
Yd5
Yd5
1
1
1
1
0
0
15
Dyn7
Dyn1
Yy6
Yd5
0
0
0
0
1
0
16
Dd8
Dd2
Yd7
Yd5
1
0
0
0
1
0
17
Dd0
Dd6
Yd11
Yd5
0
1
0
0
1
0
18
Dd0
Dd6
Yy0
Yy6
1
1
0
0
1
0
19
Dy1
Dy7
Yd1
Yy6
0
0
1
0
1
0
20
Dy5
Dy11
Yd5
Yy6
1
0
1
0
1
0
21
Dd6
Dd0
Yy6
Yy6
0
1
1
0
1
0
22
Dy7
Dy1
Yd7
Yy6
1
1
1
0
1
0
23
Dy11
Dy5
Yd11
Yy6
0
0
0
1
1
0
24
Dyn11
Dyn5
Yy0
Yd7
1
0
0
1
1
0
25
Dd0
Dd6
Yd1
Yd7
0
1
0
1
1
0
26
Dd4
Dd10
Yd5
Yd7
1
1
0
1
1
0
27
Dyn5
Dyn11
Yy6
Yd7
0
0
1
1
1
0
28
Dd6
Dd0
Yd7
Yd7
1
0
1
1
1
0
29
Dd10
Dd4
Yd11
Yd7
0
1
1
1
1
0
30
Dyn7
Dyn1
Yy0
Yd11
1
1
1
1
1
0
31
Dd8
Dd2
Yd1
Yd11
0
0
0
0
0
1
32
Dd0
Dd6
Yd5
Yd11
1
0
0
0
0
1
33
Dyn1
Dyn7
Yy6
Yd11
0
1
0
0
0
1
34
Dd2
Dd8
Yd7
Yd11
1
1
0
0
0
1
35
Dd6
Dd0
Yd11
Yd11
1
2
3 4
5 6
I II
(2
(3
Check-
sum (
1
Power transformer
vector group
Switchgroup SG1
Relay connection
group
HV side
LV side
B
1) When comparing the checksum displayed by the relay with the checksum of switches 1…6
the weighting factors of switch 7 and 8 must be added to the latter checksum.
2) I refers to the basic coupling I of the current transformers, i.e. inside OR outside earthings,
c.f. application example 4 of the description “Biased differential relay SPAD 330 C,
34 SPAD 4 EN 1”
3) II refers to the basic coupling II of the current transformers, i.e. inside AND outside earthings,
c.f. application example 5 of the description “Biased differential relay SPAD 330 C,
34 SPAD 4 EN 1”