9
Switchgroup SG3 is a so called software switch-
group, which is located in the fourth submenu
of switchgroup SG1. The front panel push-
buttons STEP and RESET can be programmed
with switches SG3/1…3. Switches SG3/4…8
are not in use. The default value for SG3 is 0.
SG3/1
SG3/2
SG3/3
Push-button
Clear
Reset
Erase
start/trip
latched
memorized
LED's
relays
values
STEP
0
0
0
RESET
x
STEP & RESET
x
x
x
STEP
x
1
0
0
RESET
x
STEP & RESET
x
x
x
STEP
x
x
0
1
0
RESET
x
STEP & RESET
x
x
x
STEP
0
0
1
RESET
x
x
STEP & RESET
x
x
x
STEP
x
1
0
1
RESET
x
x
STEP & RESET
x
x
x
The PC board of the relay module holds a
switchgroup SGB including switches 1...8.
Switches 1...3 are used for selecting the starting
signals for a possible auto-reclose module,
whereas switches 4...8 are used for routing
blocking signals to the overcurrent module in
various protection relays. The functions of the
selector switchgroup SGB is described in the
general part of the manual of the concerned
protection relay.
Measured data
The measured values are displayed by the
rightmost three digits on the display. The rele-
vant measured data are indicated by a lit indica-
tor on the front panel.
Indicator
Measured data
I
L1
Line current on phase L1 as a multiple of the rated current I
n
.
I
L2
Line current on phase L2 as a multiple of the rated current I
n
.
I
L3
Line current on phase L3 as a multiple of the rated current I
n
.
NOTE! The rated current I
n
is the rated current of the energizing input taken in use in the concerned
protection relay.