30
Data
Code
Data
Values
direction
Memorized I> start signal
O21
R
0 = signal not active
1 = signal active
Memorized I> operate signal
O22
R
0 = signal not active
1 = signal active
Memorized I>> start signal
O23
R
0 = signal not active
1 = signal active
Memorized I>> operate signal
O24
R
0 = signal not active
1 = signal active
Memorized I
0
> start signal
O25
R
0 = signal not active
1 = signal active
Memorized I
0
> operate signal
O26
R
0 = signal not active
1 = signal active
Memorized I
0
>> start signal
O27
R
0 = signal not active
1 = signal active
Memorized I
0
>> operate signal
O28
R
0 = signal not active
1 = signal active
Memorized output signal TS1
O29
R
0 = signal not active
1 = signal active
Memorized output signal SS1
O30
R
0 = signal not active
1 = signal active
Memorized output signal SS2
O31
R
0 = signal not active
1 = signal active
Memorized output signal SS3
O32
R
0 = signal not active
1 = signal active
Memorized output signal TS2
O33
R
0 = signal not active
1 = signal active
PRESENT SETTING VALUES
Present start value for stage I>
S1
R
0.5...5.0 x I
n
Present operate time or time
S2
R
0.05...300 s
multiplier for stage I>
0.05…1.0
Present start value for stage I>>
S3
R
0.5...40 x I
n
999 = not in use (
∞
)
Present operate time for stage I>>
S4
R
0.04...300 s
Present start value for stage I
0
>
S5
R
0.1...0.8 x I
n
Present operate time or time
S6
R
0.05...300 s
multiplier for stage I
0
>
0.05…1.0
Present start value for stage I
0
>>
S7
R
0.1...10.0 x I
n
999 = not in use (
∞
)
Present operate time for stage I
0
>>
S8
R
0.05...300 s
Present checksum of
S9
R
0...255
switchgroup SGF1
Present checksum of
S10
R
0...255
switchgroup SGF2
Present checksum of
S11
R
0...255
switchgroup SGB
Present checksum of
S12
R
0...255
switchgroup SGR1
Present checksum of
S13
R
0...255
switchgroup SGR2
Present checksum of
S14
R
0...255
switchgroup SGR3