19
Dimensions and
instructions for
mounting
The relay is housed in a normally flush-mounted
case. The relay can also be arranged for semi-
flush mounting with the use of a 40 mm, 80 mm
or 120 mm raising frame, which reduces the
depth behind the panel by the same dimension.
The type designation of the raising frames are
SPA-ZX 111 for the 40 mm frame, SPA-ZX
112 for the 80 mm frame and SPA-ZX 113 for
the 120 mm frame. A surface mounting case
SPA-ZX 110 is also available.
The relay case is made of an extruded, beige
aluminium profile.
A cast aluminium alloy mounting frame with
rubber gasket provides a degree of protection
by enclosure to IP 54 between the relay case
and the panel surface when the relay is panel
mounted.
The relay case is completely with a hinged
gasketed, clear, UV-stabilized polycarbonate
cover with a sealable fastening screw. The de-
gree of protection by enclosure of the cover is
also IP 54.
A terminal strip and two multipole connectors
are mounted on the back of the relay case to
facilitate all input and output connections. To
each heavy duty terminal, i.e. measuring input,
power or closing output, one 6 mm
2
,
one 4 mm
2
or one or two 2.5 mm
2
wires can be connected.
No terminal lugs are needed. The three signal-
ling inputs are available on a six pole detach-
able connector and the serial bus connection is
using a 9-pin D-type connector.
Example
1. Quantity and type designation
15 pcs SPAJ 160 C
2. Ordering number
RS 611 051 - AA
3. Rated frequency
f
n
= 50 Hz
4. Auxiliary voltage
U
aux
= 110 V dc
5. Accessories
15 pcs matching modules SPA-ZC 21 MM
2 pcs fibre optical cables SPA-ZF MM 100
6. Special requirements
-
Information
required with
order
Raising frame
SPA-ZX 111
SPA-ZX 112
SPA-ZX 113
176
136
96
74
114
154
a
b
a
b
Panel cut-out
129 ±1
139 ±1
142
162
136
30
34
250
186
216