26
Data
Code
Data flow Value range
direction
Number of startings of stage I
a
>
V1
R
0...255
Number of startings of stage I
b
>
V2
R
0...255
Number of startings of stage
∆
I
1
>
V3
R
0...255
Number of startings of stage
∆
I
2
>
V4
R
0...255
Number of startings of stage I<
V5
R
0...255
Phase condition during trip
V6
R
1 = I
b
>(L3), 2 = I
b
>(L2),
4 = I
b
>(L1), 16 = I
a
>(L3),
32 = I
a
>(L2), 64 = I
a
>(L1)
Operation indicator
V7
R
0...9
CONTROL PARAMETERS
Resetting of output relays at self-holding
V101
W
1 = reset
Resetting of output relays and registers
V102
W
1 = reset
Event mask word for I
a
> and I
b
>
stage events
V155
R,W
0...255, see "Event codes"
Event mask word for
∆
I
1
> and
∆
I
2
>
stage events
V156
R,W
0...255, see "Event codes"
Event mask word for I< or externally
controlled events
V157
R,W
0...255, see "Event codes"
Event mask word for output signal events
V158
R,W
0...1023, see "Event codes"
Opening of password for remote settings
V160
W
1...999
Changing or closing of password
for remote settings
V161
W(P)
0...999
Activating of self-supervision output
V165
W
1 = self-supervision output
is activated and IRF led
turned on
0 = normal mode
EEPROM formatting
V167
W(P)
2 = formatted
Internal error code
V169
R
0...255
Data communication address of the module V200
R,W
1...254
Data transfer rate
V201
R,W
4800 or 9600 Bd (R)
4.8 or 9.6 kBd (W)
Programme version number
V205
R
081_
Event register reading
L
R
time, channel number
and event code
Re-reading of event register
B
R
time, channel and
event code
Type designation of the module
F
R
SPCJ 4D40
Reading of module status data
C
R
0 = normal state
1 = module been subject
to automatic reset
2 = overflow of event
register
3 = events 1 and 2 together
Resetting of module state data
C
W
0=resetting
Time reading and setting
T
R,W
0.000...59.999 s
R = data to be read from the unit
W = data to be written to the unit
(P) = writing enabled by a password