background image

3

Control
push-buttons

The front panel of the relay module contains
two push buttons. The RESET / STEP push
button is used for resetting operation indicators
and for stepping forward or backward in the
display main menu or submenus. The PRO-
GRAM push button is used for moving from a

certain position in the main menu to the corre-
sponding submenu, for entering the setting
mode of a certain parameter and together with
the STEP push button for storing the set values.
The different operations are described in the
subsequent paragraphs in this manual.

Display

The measured and set values and the recorded
data are shown on the display of the protection
relay module. The display consists of four digits.
The three green digits to the right show the
measured, set or recorded value and the leftmost
red digit shows the code number of the register.
The measured or set value displayed is indicated
by  the adjacent yellow LED indicator on the
front panel. When a recorded fault value is being
displayed the red digit shows the number of the
corresponding register. When the display func-
tions as an operation indicator the red digit
alone is shown.

When the auxiliary voltage of a protection relay
module is switched on the module initially tests
the display by stepping through all the segments
of the display for about 15 seconds. At first the
corresponding segments of all digits are lit one
by one clockwise, including the decimal points.
Then the center segment of each digit  is lit one
by one.  The  complete sequence is carried out
twice. When the test is finished the display turns
dark. The testing can be interrupted by pressing
the STEP push button. The protection func-
tions of the relay  module are alerted throughout
the testing.

Display main menu

Any data required during normal operation are
accessible in the main menu i.e. present meas-
ured values, present setting values and recorded
parameter values.

The data to be shown in the main menu are
sequentially called up for display by means of
the STEP push button. When the STEP push
button is pressed for about one second, the
display moves forward in the display sequence.
When the push button is pressed for about 0.5
seconds, the display moves backward in the
display sequence.

From a dark display only forward movement is
possible. When the STEP push button is pushed
constantly, the display continuously moves for-
ward stopping for a while in the dark position.

Unless the display is switched off by stepping to
the dark point, it remains lit for about 5 minutes
from the moment the STEP push button was
last pushed. After the 5 minutes' time-out the
dispaly is switched off.

Display submenus

Less important values and values not very often
set are displayed in the submenus. The number
of submenus varies with different relay module
types. The submenus are presented in the de-
scription of the concerned protection relay
module.

A submenu is entered from the main menu by
pressing the PROGRAM push button for about
one second. When the push button is released,
the red digit of the display starts flashing, indi-
cating that a submenu has been entered. Going
from one submenu to another or back to the
main menu follows the same principle as when
moving from the main menu display to another;

the display moves forward when the STEP push
button is pushed for one second and backward
when it is pushed for 0.5 seconds. The main
menu has been re-entered when the red display
turns dark.

When a submenu is entered from a main menu
of a measured or set value indicated by a LED
indicator, the indicator remains lit and the ad-
dress window of the display starts flashing. A
submenu position is indicated by a flashing red
address number alone on the dispaly without
any lit set value LED indicator on the front
panel.

Summary of Contents for SPAM 150 C

Page 1: ...n I s 3I 3 I RS 641 Ser No SPAM 150 C Uaux SPCJ 4D34 REGISTERS OPER IND 0 0 0 0 0 1 2 3 4 5 6 7 8 n L3 n L1 n L2 1 2 3 4 5 6 7 8 o 2 5 9 EXT TRIP 9 t 955D I I I I I I I I I I I 80 265V 18 80V n I I 5A...

Page 2: ...nitoring all three phases the thermal replica is adjustable both for protected objects with or protected objects without hot spots High set overcurrent protection operating in stantaneously or with de...

Page 3: ...ontact functions This contact information is used e g for the blocking of co operating protective re layslocatedupstreams forconnectiontoannun ciator units etc The motor protection relay contains one...

Page 4: ...I START I RESTART INHIBIT RESTART INHIBIT RELAY RESET i a t EXTERNAL TRIP I x t 2 s s 25 26 27 1 2 3 4 5 6 7 8 9 1 A 5 A 1 A 5 A 1 A 5 A 1 A 5 A SERIAL PORT SPA ZC_ Rx Tx 61 62 U aux SGR1 7 SGR1 6 SG...

Page 5: ...and output relay module SPTU 240 R2 or SPTU 48 R2 with a normally open trip contact SPTU 240 R3 or SPTU 48 R3 with a normally closed trip contact U3 Input module SPTE 4E3 SPA ZC Bus connection module...

Page 6: ...odule The communication mode selector switches on the bus connection module are set in position SPA The three phase currents are connected to ter minals 1 2 4 5 and 7 8 when the rated current of the s...

Page 7: ...SGR2 7 SGR1 8 SGR2 3 STALL RESTART INH SGB 3 SGR2 2 1 SG4 3 SG4 2 6x Fig 4 Control signals between the modules of the motor protection relay SPAM 150 C the measuring relay module The functions of thed...

Page 8: ...50Hz 60Hz A The operation indicator TRIP is lit when one of the protection stages operates When the protection stage resets the red indicator remains alight Indication Explanation 1 a The thermal lev...

Page 9: ...x 80 265 V ac dc 18 80 V dc Unstabilized logics voltage Operation amplifier voltage Output relay coil voltage Fig 5 Voltage levels of the power supply module A green LED indicator Uaux on the system f...

Page 10: ...A 1 A 1 A 0 25 A 0 15 A Breaking capacity for ac 5 A 5 A Signalling contacts Terminals 70 71 72 68 69 77 78 80 81 Rated voltage 250 V dc ac Rated current 5 A Make and carry for 0 5 s 10 A Make and ca...

Page 11: ...n unit Setting range for I0 1 0 100 In Operate time t0 0 05 30 s Attenuation of the third harmonic typ 20 dB Phase unbalance unit Basic sensitivity I stabilized to phase current levels below I 10 40 x...

Page 12: ...st IEC 60255 22 2 and IEC 61000 4 2 contact discharge 6 kV air discharge 8 kV Fast transient disturbance test IEC 60255 22 4 and IEC 61000 4 4 power supply 4 kV I O ports 2 kV Mechanical tests tested...

Page 13: ...information about checking overhaul and re calibration of the relay Note Numerical protection relays contain electronic circuitswhichareliabletoseriousdamagedueto electrostatic discharge Before removi...

Page 14: ...over is also IP 54 A terminal strip and two multipole connectors are mounted on the back of the relay case to facilitate all input and output connections To each heavy duty terminal i e the measuring...

Page 15: ...indicator Internal Relay Fault Display 1 3 digits Reset Step push button Programming push button Trip indicator Module type designation Fastening screw Indicators for measured quantities Indicators fo...

Page 16: ...SGB SGR 4 Settings 4 Setting mode 4 Example 1 Setting of relay operation values 7 Example 2 Setting of relay switchgroups 9 Recorded information 11 Trip test function 12 Example 3 Forced activation of...

Page 17: ...ion are accessible in the main menu i e present meas ured values present setting values and recorded parameter values The data to be shown in the main menu are sequentially called up for display by me...

Page 18: ...cation bus 2 By an external control signal BS1 BS2 or RRES BS3 3 Via the push buttons of the relay module see submenu 4 of register A Setting mode Generally when a large number of settings is to be al...

Page 19: ...willshowthreedashes toindicatethenon tripping mode The serial communication is operativeandallmainandsubmenuesareacces sible In the non tripping mode unnecessary trippings are avoided and the settings...

Page 20: ...se L2 Event n 2 value of phase L2 Latest memorized event n value of phase L2 2 1 2 Event n 1 value of phase L3 Event n 2 value of phase L3 Latest memorized event n value of phase L3 3 1 2 Main setting...

Reviews: