background image

6

vides a latching function after any trip opera-
tion.  After having latched the output relay must
be manually reset or reset by remote control.

The trip alarm signals from the relay module are
obtained via output relays B and C. The signals
to be routed to these relays are selected with
switches1...7 of switchgroup SGR1 and switches
4...8 of switchgroup SGR2 of the  relay module.
Normally the output  relays B and C are given
such a configuration that a thermal prior alarm
is obtained  over relay C and the trip signals of
the protection units are linked to output relay B
to form an auxiliary trip signal. This is also the
default setting of the relay on delivery from the
factory.

The signals to be routed to  the output relay  D
are selected with switches 1, 2 and 3 of software
switchgroup SGR2 in the main menu of the
relay module. Switch SGR2/1 routes the ther-
mal prior alarm, switch SGR2/2 routes the
startup information for the motor and switch
SGR2/3 routes the start signal of the high-set
overcurrent stage to output relay D.

Output relay E, terminals 74-75, is a heavy duty
output relay capable of controlling a circuit
breaker, as  the main trip relay A.  Relay E is used
for controlling the restart of the motor. If the
thermal capacity used exceeds the set restart
inhibit level of the thermal unit, if the allowed
maximum cumulative start-up count is exceeded
or if the external restart inhibit signal is active
the output relay E prevents a motor restart
attempt.  This also applies to a condition where
the protective relay is out of auxiliary voltage or
the relay is faulty.

Output relay F, terminals 70-71-72, operates as
the output relay of the integrated self-supervi-
sion system. The relay operates on the closed-
circuit principle, thus under normal service con-
ditions the contact gap 70-72 is closed. If a fault
is detected by the self-supervision system, or if
the auxiliary supply fails, the output relay drops
off, providing an alarm signal by closing the NO
contact 71-72.

The relay is connected to the SPA data bus by
means of bus connection module type SPA-ZC
17 or SPA-ZC21. The bus connection module
is connected to the D type connector marked
SERIAL PORT on the rear panel of the relay.
The fibre-optic cables are connected to the
connectors Tx and Rx of the bus connection
module. The communication mode selector
switches on the bus connection module are set
in position "SPA".

The three phase currents are connected to ter-
minals 1-2, 4-5 and 7-8, when the rated current
of the secondary circuits is I

n

 = 5 A. When using

current transformers with a rated current of 1 A,
terminals 1-3, 4-6 and 7-9 are used. The ther-
mal overload protection may  also be used in
single-phase or two-phase applications, in this
case inputs not used may be left unconnected.

To get a proper operation of the unbalance and
incorrect phase sequence protection in a two-
phase application, the two phase currents should
be  summed in the third phase current input. In
single-phase applications, wiring the phase cur-
rent through two or three current inputs in series
may slightly increase the operating speed of the
relay and stabilize operation of the thermal unit.

The neutral current of the earth-fault protection
is connected to terminals 25-26 when the rated
current is 5 A and to terminals 25-27 when the
rated current is 1 A.

The control input 10-11 can be used in five
different ways:
- as the control input controlled by a motor

speed switch in Ex-type applications

- as the control input of an external blocking

signal for blocking the operation of  the unbal-
ance or earth-fault protection units

- as the control  input for an external trip signal
- as the control input for unlatching the trip relay
- as the control input for the restart enable relay.

The designed function is selected by means of
switches 1...8 of switchgroup SGB in the main
menu of the protection relay module.

The auxiliary supply voltage of the relay  is
connected to the terminals 61-62. At d.c. auxil-
iary supply voltage the positive lead is connected
to terminal 61. The accepted input voltage
range is determined by the type of power supply
and output relay module inserted in the relay
case. For further details see the description of the
power supply module. The accepted auxiliary
voltage range of the relay is indicated on the
front panel.

Output relay A provides the CB tripping com-
mands when the operate time of a protective
unit has elapsed. The earth-fault unit can be
made non-tripping, i.e. only signalling, with
switch 8 of switchgroup SGR1. On delivery from
factory all protective units are selected to per-
form tripping. A latching function of the output
relay A can be selected by means of switches
SGB/7 and SGB/8. Switch SGB/7 gives a latch-
ing function after a short-circuit, an earth-fault
or an unbalance tripping. Switch SGB/8 pro-

Connections

Summary of Contents for SPAM 150 C

Page 1: ...n I s 3I 3 I RS 641 Ser No SPAM 150 C Uaux SPCJ 4D34 REGISTERS OPER IND 0 0 0 0 0 1 2 3 4 5 6 7 8 n L3 n L1 n L2 1 2 3 4 5 6 7 8 o 2 5 9 EXT TRIP 9 t 955D I I I I I I I I I I I 80 265V 18 80V n I I 5A...

Page 2: ...nitoring all three phases the thermal replica is adjustable both for protected objects with or protected objects without hot spots High set overcurrent protection operating in stantaneously or with de...

Page 3: ...ontact functions This contact information is used e g for the blocking of co operating protective re layslocatedupstreams forconnectiontoannun ciator units etc The motor protection relay contains one...

Page 4: ...I START I RESTART INHIBIT RESTART INHIBIT RELAY RESET i a t EXTERNAL TRIP I x t 2 s s 25 26 27 1 2 3 4 5 6 7 8 9 1 A 5 A 1 A 5 A 1 A 5 A 1 A 5 A SERIAL PORT SPA ZC_ Rx Tx 61 62 U aux SGR1 7 SGR1 6 SG...

Page 5: ...and output relay module SPTU 240 R2 or SPTU 48 R2 with a normally open trip contact SPTU 240 R3 or SPTU 48 R3 with a normally closed trip contact U3 Input module SPTE 4E3 SPA ZC Bus connection module...

Page 6: ...odule The communication mode selector switches on the bus connection module are set in position SPA The three phase currents are connected to ter minals 1 2 4 5 and 7 8 when the rated current of the s...

Page 7: ...SGR2 7 SGR1 8 SGR2 3 STALL RESTART INH SGB 3 SGR2 2 1 SG4 3 SG4 2 6x Fig 4 Control signals between the modules of the motor protection relay SPAM 150 C the measuring relay module The functions of thed...

Page 8: ...50Hz 60Hz A The operation indicator TRIP is lit when one of the protection stages operates When the protection stage resets the red indicator remains alight Indication Explanation 1 a The thermal lev...

Page 9: ...x 80 265 V ac dc 18 80 V dc Unstabilized logics voltage Operation amplifier voltage Output relay coil voltage Fig 5 Voltage levels of the power supply module A green LED indicator Uaux on the system f...

Page 10: ...A 1 A 1 A 0 25 A 0 15 A Breaking capacity for ac 5 A 5 A Signalling contacts Terminals 70 71 72 68 69 77 78 80 81 Rated voltage 250 V dc ac Rated current 5 A Make and carry for 0 5 s 10 A Make and ca...

Page 11: ...n unit Setting range for I0 1 0 100 In Operate time t0 0 05 30 s Attenuation of the third harmonic typ 20 dB Phase unbalance unit Basic sensitivity I stabilized to phase current levels below I 10 40 x...

Page 12: ...st IEC 60255 22 2 and IEC 61000 4 2 contact discharge 6 kV air discharge 8 kV Fast transient disturbance test IEC 60255 22 4 and IEC 61000 4 4 power supply 4 kV I O ports 2 kV Mechanical tests tested...

Page 13: ...information about checking overhaul and re calibration of the relay Note Numerical protection relays contain electronic circuitswhichareliabletoseriousdamagedueto electrostatic discharge Before removi...

Page 14: ...over is also IP 54 A terminal strip and two multipole connectors are mounted on the back of the relay case to facilitate all input and output connections To each heavy duty terminal i e the measuring...

Page 15: ...indicator Internal Relay Fault Display 1 3 digits Reset Step push button Programming push button Trip indicator Module type designation Fastening screw Indicators for measured quantities Indicators fo...

Page 16: ...SGB SGR 4 Settings 4 Setting mode 4 Example 1 Setting of relay operation values 7 Example 2 Setting of relay switchgroups 9 Recorded information 11 Trip test function 12 Example 3 Forced activation of...

Page 17: ...ion are accessible in the main menu i e present meas ured values present setting values and recorded parameter values The data to be shown in the main menu are sequentially called up for display by me...

Page 18: ...cation bus 2 By an external control signal BS1 BS2 or RRES BS3 3 Via the push buttons of the relay module see submenu 4 of register A Setting mode Generally when a large number of settings is to be al...

Page 19: ...willshowthreedashes toindicatethenon tripping mode The serial communication is operativeandallmainandsubmenuesareacces sible In the non tripping mode unnecessary trippings are avoided and the settings...

Page 20: ...se L2 Event n 2 value of phase L2 Latest memorized event n value of phase L2 2 1 2 Event n 1 value of phase L3 Event n 2 value of phase L3 Latest memorized event n value of phase L3 3 1 2 Main setting...

Reviews: