75
TAG DISPLAY ENABLE
OPERATING PAGE TAG
FRAME TO CONFIGURE
NONE
FRAME TYPE
DIGITAL
TOTALISER
STANDARD
OFF
OFF
FRAME SOURCE
DIGITAL I/P
CHART SPEED
LOGIC EQN
POWER FAILURE
REAL TIME ALM
PROCESS ALARM
DIGITAL
TOTALISER
FRAME SOURCE
TOTALISER T
STANDARD
FRAME SOURCE
Analog Input
Maths Result M
SELECT PEN VALUES
PENS 1..3
OPERATING PAGE
CONFIGURATION
YES
NO
YES
PEN VALUE
PENS 4..6
FRAME LOWER LINE
BARGRAPH
CHANNEL TAG
PEN VALUE
TOTALISER
or
DIGITAL
6789:;<=>?@ABCDEF
NO
6
CONFIGURATION – ADVANCED LEVEL…
…6.3.2
Operating Pages 1 and 2 Configuration Page
Tag Display Enable
Select
YES
to enable the
Operating Page 1
tag (not available for
Operating
Page 2
.
Page Tag
A page name of up to twenty characters can
be set on the upper display – see Front Fold-
out.
Frame to Configure
Eight separate frames can be programmed for each page to display analog,
digital or totalizer sources. These are displayed in sequence in
Operating Page 1 or
2
.
On entry the default is
NONE
.
Select the frame to configure.
Frame Type
Select the frame required from the five frame types available (see Fig. 6.6, page 72):
PEN VALUE
– Displays the inputs assigned to the pens
Up to 3 inputs can be displayed in one frame
DIGITAL
– Any one of up to 47 sources from digital inputs, alarms,
logic equations or chart speeds
TOTALISER
– Any one of six totalizers
STANDARD
– Any one of up to 12 analog inputs (see Section 4.2) or four
math functions
OFF
– All but frame 1 of
Operating Page 1
can be set to
OFF
Frame Source (Standard)
Select any one of up to 12 analog inputs (A1 to A6, B1 to B6, depending on the
options fitted – see Section 4.2) or four math functions.
Frame Lower Line
Select one of the following:
BARGRAPH
– Displays a 100 segment bar graph.
CHANNEL TAG
– Displays the tag allocated to the selected input source
Frame Source (Totalizer)
Select any one of up to six totalizers (T1 to T6).
Frame Source (Digital)
Select the frame source from the six different digital input sources available:
DIGITAL I/P
– Any one of up to 19 digital inputs
CHART SPEED
– Any one of three pre-defined chart speeds
LOGIC EQN
– Any one of up to 10 logic equations
POWER FAILURE
– The power failure alarm
REAL TIME ALM
– Either of the two real time alarms
PROCESS ALARM
– Any one of 12 process alarms
Select Pen Values
Select required pen value (1, 2 and 3) or (4, 5 and 6).
Return to
Frame to Configure
frame.