41-766.7
SSV-T and SSC-T High Drop-out Relay
2
device. A magnetic armature, to which leaf-spring
mounted contacts are attached, is attracted to the
magnetic core upon energization of the switch. When
the switch closes, the moving contacts bridge two
stationary contacts, completing the trip circuit. Also
during this operation, two fingers on the armature
deflect a spring located on the front of the switch
which allows the operation indicator target to drop.
The target is reset from the outside of the case by a
push rod located at the bottom of the cover.
3.0 OPERATION
The block diagrams of the SSV-T and SSC-T are
shown in Figures 1, 2 and 3 (page 4 and page 5) and
the internal schematic are shown in Figures 4, 5, and
6 (page 5 and page 6). For overvoltage and overcur-
rent application, the transistor Q2 is normally not
conducting and the telephone relay is de-energized.
The transistor Q1 or current is applied to the primary
of the transformer (T) a voltage is produced on the
secondary side that tis proportional to the input. The
potentiometer (R2) is for the pick-up setting. If the
voltage from rectifier (Z1, Z2, and C2) is large
enough to exceed the breakdown voltage of zener
diode Z5, the zener diode conducts to turn on the
transistor Q2 and operate the telephone relay.
For undervoltage application, the transistors Q1 and
Q2 are normally conducting and the telephone relay
is pulled in. As soon as the input voltage drops below
the setting, the transistor Q2 is turned off and the
telephone relay is released.
4.0 CHARACTERISTICS
4.1
OVERCURRENT RELAY SSC-T
4.2
OVER/UNDERVOLTAGE RELAY SSV-T
4.3
TRIP CIRCUIT
The main contacts will safely close 30 amperes at
250 volts dc and the seal in contacts of the indicating
contactor switch (when supplied) will safely carry this
current long enough to trip a circuit breaker.
Table 1: SSC-T Burden (60 Hertz)
Range (Amps)
Pickup Current Setting
Lowest Setting
Highest Setting
VA
P.F. Angle ø
VA
P.F. Angle ø
.05 - 2.0
2.0 - 8.0
4.0 - 8.0
10.0 - 40.0
0.5
0.5
0.5
0.8
8.5°
8.5°
8.5°
10.0°
4.0
5.0
5.0
8.0
12.5°
12.5°
12.5°
10.5°
Range
Continuous
Rating
One
Second
Rating
0.5 - 2 amps
2.0 - 8 amps
4.0 - 16 amps
10 - 40 amps
2 amps
8 amps
10 amps
10 amps
28 amps
112 amps
280 amps
280 amps
Operating
Frequency:
50/60 Hz
Temperature
Error:
2% between 20°C
and 65°C
Dropout Ratio:
90% to 98%
Response Time:
Pickup Time = 10 - 13 ms
Dropout Time = 10 - 26 ms
For 2 to 15 times pickup setting value (Figure 10)
Transient
Overreach:
5%
Burden:
See Table 1 below
Telephone Relay
Contacts:
0.1 amps at 125 Vdc
Range:
60- 140 Volts
140 - 320 Volts
280 - 640 Volts
Continuous Rating: Highest voltage of range setting
Operating
Frequency:
50/60 Hz
Temperature Error:
2% between -20°C and +65°C
Dropout Ratio:
92% to 99% (Figure 13)
Response Time:
Pickup Time - 7– 10 ms
Dropout Time – 14 - 40 ms
(Figure 9)
Burden:
1 VA at 120 volts 60 Hz
Telephone Relay
Contacts:
0.1 Amps at 125 Vdc
Summary of Contents for SSV-T
Page 1: ......
Page 10: ......
Page 11: ...SSV T and SSC T High Drop out Relay 41 766 7 11 THIS SPACE RESERVED FOR NOTES ...