ADDENDUM
11
FACTORY TRIM
Use this option if factory setting is to be used for calibration.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select SENSOR TRIM, or select calibration option
with down-arrow key and refer to the appropriate
section. Press
when done.
Select FACTORY TRIM.
C A LI-
B R AT E
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
→
SENSOR TRIM
D-TO-A ADJUST
PV BIAS
SET OUTPUT %
ENTER
E N T E R
FULL TRIM
ZERO TRIM
→
FACTORY TRIM
STATIC TRIM
E N T E R
ID TAGNAME
READY