EQN TEMPERATURE TRANSMITTER
CALIBRATION
H - 6
Apply 0 mV to the transmitter.
Apply 25 mV to the transmitter.
Enter the field device ambient temperature in
degrees Celsius using the number keypad. The sur-
rounding room temperature can be used for this tem-
perature value.
Adjust the transmitter output using the up and down
arrow keys.
Adjust the transmitter output using the up and down
arrow keys.
Bench calibration is complete.
Key
Display
Comments
E N T E R
APPLY 0 mV
SIGNAL
THEN HIT ENTER
E N T E R
APPLY 25 mV
SIGNAL
THEN HIT ENTER
E N T E R
ENTER TRANSMITTER
AMBIENT TEMP.
nn.nn C
E N T E R
ADJUST TO 4 mA
THEN HIT ENTER
E N T E R
ADJUST TO 20 mA
THEN HIT ENTER
E N T E R
ID TAGNAME
READY