TZID/AZH POSITIONER
SPECIAL FEATURE
M - 11
Edit the go pulse value.
If the actuator is still, the controller provides an
amplified output signal for the defined pulse time to
achieve a rapid startup of the actuator.
NOTE:
If overshoot occurs, reduce go pulse value.
Edit the output offset percentage of the actuator.
Output offset linearizes the action of the used I/P
module and enables rapid control until reaching the
set point. An output offset between 40% and 80% is
acceptable for most actuators.
Edit the noise band of A/D conversion.
ADC
noise band can be used as an interference indi-
cator. If the noise is big, the measuring accuracy and
control reaction is affected. Normally an acceptable
ADC noise band value is between 0.03% and 0.05%.
Select the
I/P MODULE
setting.
This defines the triggering or safe position to the
built-in I/P module. The setting must be the same as
the existing I/P module in the TZID/AZH positioner.
Select
YES
if changes were made to the parameters.
Select
YES
to make the changes permanent.
Key
Display
Comments
E N T E R
GO PULSE (mSEC)
UP:
nn.n
DOWN:
nn.n
E N T E R
OUTPUT OFFSET (%)
UP:
nn.n
DOWN:
nn.n
E N T E R
ADC NOISE BAND
nn.nnn%
E N T E R
I/P MODULE:
UNIPOLAR, SINGLE ACT
BIPOLAR, SINGLE ACT
UNIPOLAR, DOUBLE ACT
BIPOLAR, DOUBLE ACT
E N T E R
SEND
CONTROL PARAMETERS ?
NO
→
YES
E N T E R
MAKE CHANGES
PERMANENT ?
NO
→
YES
E N T E R
ID TAGNAME
READY