TB82 TRANSMITTER
SPECIAL FEATURE
N - 12
SPECIAL FEATURE
The following section details unique special feature functions for the
TB82.
Sensor Data
This procedure describes how to view sensor data.
Use the arrow keys to adjust output shown on the
meter to 20 mA.
Key
Display
Comments
E N T E R
ADJUST TO 20 mA
THEN HIT ENTER
E N T E R
ID TAGNAME
READY
Key
Display
Comments
Select
SENSOR DATA
.
View slope and offset of the process.
Valid slope values are 40% to 150%. Valid offset val-
ues are -1,000 to +1,000 mV.
View slope and offset of the temperature.
Valid range for slope is 0.2 to 1.5. Valid range for off-
set is -40° to 40°C.
S P E C IA L
F E AT U R E
FIX/CANCEL OUTPUT
→
SENSOR DATA
HART SP. FEATURE
E N T E R
PROCESS
SLOPE :
nn.nnnn
OFFSET:
nn.nnnn
E N T E R
TEMPERATURE
SLOPE :
nn.nnnn
OFFSET:
nn.nnnn
E N T E R
ID TAGNAME
READY