Controlled Switching — Buyer´s Guide
K-
Edition 2, 2006-09
Technical Data
Technical Information
Technical Data for Switchsync
TM
Type of controller
E113 and E213
F236
L183
T183
Power supply
Power consumption
0 - 250 V AC/DC
< 4 VA
0 - 250 V AC/DC
< 4 VA
0 - 250 V AC/DC
< 4 VA
0 - 250 V AC/DC
< 4 VA
Operating command
Duration
48 - 250 V DC
0.5 - 2 s
48 - 250 V DC
0.5 - 2 s
48 - 250 V DC
0.5 - 2 s
48 - 250 V DC
0.5 - 2 s
Reference voltage detector
Power consumption
35 - 50 V AC ,5 - 66 Hz
< 0. VA
35 - 50 V AC, 5 - 66 Hz
< 0. VA
35 - 50 V AC, 45 - 66 Hz
< 0. VA
35 - 50 V AC, 5 - 66 Hz
< 0. VA
Current start detector
Short-time current
Power consumption
0.5 - 5.0 A
00 A, s
0.66 VA at 5.0 A
0.5 - 5.0 A
00 A, s
0.66 VA/input at 5.0 A
-
-
Voltage start detector
Power consumption
AC
DC
48 - 250 V AC/DC
< .5 VA
< 0.2 VA
48 - 250 V AC/DC
< .5 VA/input
< 0.2 VA/input
48 - 250 V DC
-
< 0.2 VA/input
48 - 250 V DC
-
< 0.2 VA/input
Trip information
Power consumption
-
-
48 - 250 V DC
< 0.2 VA
48 - 250 V DC
< 0.2 VA
CB status detector
Power consumption
-
-
48 - 250 V DC
< 0.2 VA
48 - 250 V DC
< 0.2 VA
Load voltage input
Input impedance
-
-
55-70 or 00-20 V AC
> 200 k
Ω
55-70 or 00-20 V AC
> 200 k
Ω
Cross-section area of
connecting leads
≤
4 mm
2
≤
4 mm
2
≤
4 mm
2
≤
4 mm
2
Socket screws
Hollow socket screws for easy plug-in connection of recording device during commissioning tests.
Ambient temperature
-30 - +55 °C
-30 - +55 °C
-30 - +55 °C
-30 - +55 °C
Immunity tests
Power interruption test
IEC 60255-
IEC 6000-4-
EN 6000-4-
IEC 6000-4-
EN 6000-4-
IEC 6000-4-
EN 6000-4-
Power frequency withstand 2
kV, 1 min.
IEC 60255-5
IEC 60255-5
IEC 60255-5
IEC 60255-5
Surge/Transients
IEC 60255-4 Cl. III
IEC 6000-4-5
EN 6000-4-5
IEC 6000-4-5
EN 6000-4-5
IEC 6000-4-5
EN 6000-4-5
Burst/Fast transients
IEC 60255-22-4 Cl. IV
EN 50082-2
IEC 6000-4-4
EN 6000-4-4
IEC 6000-4-4
EN 6000-4-4
IEC 6000-4-4
EN 6000-4-4
1 MHz burst transient
IEC 60255-22- Cl. III
IEC 60255-22- Cl. III
IEC 60255-22- Cl. III
IEC 60255-22- Cl. III
Electrostatic discharge
EN50082-2
(IEC 6080-2)
IEC 6000-4-2
EN 6000-4-2
IEC 6000-4-2
EN 6000-4-2
IEC 6000-4-2
EN 6000-4-2
Radiated electro-magnetic
field
IEC 6080-3
(EN50082-2)
IEC 6000-4-3
EN 6000-4-3
IEC 6000-4-3
EN 6000-4-3
IEC 6000-4-3
EN 6000-4-3
Conducted radio frequency
interference
EN 5008-2
EN 6000-4-6
IEC 6000-4-6
EN 6000-4-6
IEC 6000-4-6
EN 6000-4-6
IEC 6000-4-6
Vibrations
IEC 60068-2-29
IEC 60068-2-29
IEC 60068-2-29
IEC 60068-2-29
Emission tests
Conducted and radiated
emission
EN 5008-2
EN 550A
CISPRIA
EN 550A
CISPRIA
EN 550A
CISPRIA
Dimensions
46 x 46 x 298 mm
46 x 290 x 298 mm
46 x 290 x 298 mm
46 x 290 x 298 mm