Clear reset counters
Press ENT to begin
3.20.2
Reinitializing control setpoints due to checksum error
When a Checksum ERROR occurs the voltage control element of the
control is NOT available.
In the event a "checksum error" occurs, then the control will initiate a cycling "Checksum
Error" display. In this case the "Clear reset counters" menu item in the Utilities/
Configuration/Test menu display will change to "Init setpoints" function. To reinitialize
the control setpoints perform the following:
1.
Press the ENT (UTIL Hot Button) pushbutton to awaken the unit. The menu will
advance to "UTILITIES".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Calibration/Test
3.
Press the Down arrow pushbutton as necessary to navigate to the "Init setpoints"
screen.
4.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Init setpoints
Press ENT to begin
5.
Press the ENT pushbutton. The following will be displayed:
Confirm press ENT
Cancel press EXIT.
6.
Press ENT. The control will display the following sequence of screen displays:
Initializing....
Initialization Done
Init Setpoints
Press ENT to begin
3.21
About screens
3.21.1
Accessing the about screens from the HMI
The About screens provide the user with unit serial number and firmware version.
Section 3
1VAC388793-MB A
Operation
108
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......