3.24.2
Resetting motor seal-in failure alarm/block from TCC600
1.
Select
Setup/Alarms
from the TCC600 toolbar. TCC600 will display the
Programmable Alarm dialog screen.
2.
From the Motor Seal-in Failure Alarm reset section of the dialog screen select Reset.
3.25
Lockout alarms
3.25.1
Clearing master/follower or delta VAr peer to peer lockout alarm
from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to awaken the unit. The
menu will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, until "Paralleling" is
displayed.
4.
Press the Down arrow, as necessary, until the following will be displayed.
Clear Lockout Alarm
Ready Press ENTER
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Confirm press ENTER
Cancel press EXIT.
6.
Press the ENT pushbutton. The following sequence of screens will be displayed:
Confirm press ENTER Cleared
Clear Lockout Alarm Ready press ENTER
3.25.2
Clearing master/follower lockout alarm from TCC600
1.
Select
Utility/Master/Follower configuration
from the TCC600 toolbar. TCC600
will display the Access Level Code dialog screen.
1VAC388793-MB A
Section 3
Operation
TCC300
115
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......