Level 1: 000000 (Disabled)
•
Level 2: 222222
GUID-F319E4A5-88B6-4699-8B1B-FB4280BEBA4A V1 EN
Figure 66:
Checking Save
8.
Select
Connect
. TCC600 will attempt to connect to the target control.
9.
If TCC600® returns a Failed to Connect Error screen, then repeat Steps 6,7 and 8.
GUID-E30C4027-330B-4500-A102-756531F004F3 V1 EN
Figure 67:
Failed to Connect Error Screen
10. If Level 1 Access is not active or the proper Level 1 or Level 2 access code was
entered, then TCC600 will briefly display a "Successfully Connected Level 1/Level
2" confirmation screen, then display the connected version of the TCC600 Main
Screen with the appropriate Access Level.
11. If Level 1 Access is active and an invalid access code was entered, then TCC600 will
display a "Failed to complete Access Code Verification" error message.
Section 4
1VAC388793-MB A
TCC600
124
TCC300
User Manual