Table 23:
Reverse Power
Item
Description
Operation
Toggles between eight modes of operation:
•
Block – inhibits automatic tapchange
operation.
•
Regulate Forward (Ignore) – continues unit
action as though forward power flow continued
to exist.
•
Regulate Reverse – (calculated voltage or
measured voltage) detects a reverse power
condition and regulates according to reverse
power settings.
•
Return to Neutral – detects a reverse power
operation and drives tap position to neutral and
then stops.
•
Regulate Reverse (Measured) – allows the
control to switch it’s voltage sensing input from
a load side VT to a source side VT if one is
available and operate in Reverse Power Mode
using that input.
•
Distributed Generation – allows alternate LDC
R and X values to be applied to the control
when reverse power is detected.
•
Auto Determination – allows the control to use
the "Smart Reverse Power" feature to choose
the applicable reverse power mode, either
Distributed Generation or Regulate Reverse.
•
Auto Determination (Measured) – allows the
control to use the "Smart Reverse Power"
feature to choose the applicable reverse power
mode, either Distributed Generation or
Regulate Reverse (Measured).
The Setpoints Reverse Power section also contains
a link which displays the "Reverse Power Vendor
Cross Reference" table showing Cooper/Siemens
reverse power names and their ABB equivalents
(
).
Band Center
Adjustable from 100.0 V to 135.0 V in 0.1 V
increments with a factory setting of 120 V.
Band Width
Adjustable from 1.0 V to 10.0 V in 0.1 V increments
with a factory setting of 2.0 V.
Definite/Inverse Time
Adjustable from 1 sec. to 360 sec. in 1 second
increments with a factory setting of 30 seconds
LDC‑Z
Adjustable from 0 V to 72 V in 1 V increments with a
factory setting 0 V.
LDC Resistance
Adjustable from –72 V to +72 V in 1 V increments with
a factory setting of 0 V.
LDC Reactance
Adjustable from –72 V to +72 V in 1 V increments with
a factory setting of 0 V.
Section 4
1VAC388793-MB A
TCC600
180
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......