VLAN-ID: 0
•
VLAN-PRIORITY: 4
•
MAC Address: 01-0C-CD-00-00-10
•
APPID: 0
Also, the GOOSE dataset contains only one data which is organized as, the most
significant 4 bits will have the profile number to be activated and the rest will contain the
timer reload value.
Using this method, the IEC 61850 client should repetitively publish a GOOSE message
with the above mentioned attributes and data, before the timer reload value expires.
HeartBeat Manual Mode
The purpose of the Manual HeartBeat Mode feature is to provide a method to place the
control in Manual operation and automatically place the control back in Auto mode based
on a HeartBeat Timer setting (settable only via DNP communication). The HeartBeat
Timer setting is Object 40 "Remote Manual Timer".
The Manual HeartBeat Timer is settable from 0 to 999 Minutes. When the timer is set to
a non zero value it will place the control in HeartBeat Manual Mode (Auto operation
blocked). If the timer expires the control is placed back in auto mode. If the timer is
refreshed before it expires, the control stays in HeartBeat Manual mode.
The DNP status point (binary input Object 1) that shows if the control is in the HeartBeat
Manual Mode is: "Manual HeartBeat Status". This point will be set to 1 when placed in
manual using the Manual HeartBeat Timer only and not by any other means.
The HeartBeat Manual Mode is separate from the original comm block manual mode.
They both perform the same function, but use a different method and DNP point to activate
auto or Manual mode. When the control is in Comm Blk Manual, the Manual LED will
turn on steady as before, but when in the HeartBeat Manual mode it will flash. The
HeartBeat manual method can only be activated via the new HeartBeat timer setting point
while the old comm blk method can be activated via comms or the toggle/scamp switch as
before.
The Comm Blk mode has priority over the HeartBeat Manual mode regardless of how it
is enabled (through communication or switch input). When in HeartBeat Manual mode the
tap/voltage limit blocks are active just as before with comm blk mode, but in HeartBeat
manual the runback due to high Voltage will also be enabled. If the control is in HeartBeat
Manual mode and the comm blk manual is also turned on (via comms or switch input),
then the HeartBeat timer will continue to count down. If Comm Blk is turned off, then it
will go back to HeartBeat Manual mode unless the HeartBeat manual timer has reached
0.
Section 5
1VAC388793-MB A
System setup
320
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......