4.
Press the Down arrow, as necessary, until the following will be displayed.
Seal-In Fail Block
disable
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code.
6.
Utilizing the Up/Down arrow pushbuttons select enable, then press the ENT
pushbutton.
6.2.5.4
Setting Motor Seal-in Failure Alarm/Block from TCC600
1.
Select
Setup/Tap Settings
from the TCC600 toolbar. TCC600 will display the Tap
Settings dialog screen.
GUID-2EDBFD25-222B-4846-9AA2-CDFA5AE21B47 V1 EN
Figure 278:
Tap Settings Dialog Screen
2.
From the "Block Automatic Operation on Motor Seal-in Failure" section of the Tap
settings screen select Motor Seal-in Failure "Enable" or "Disable".
3.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
353
User Manual