NONSEQ INPUT C
6.
Utilizing the arrow pushbuttons, select the desired Input Selection 2 (Non-
Sequential or SCADA Cutout), then press the ENT pushbutton.
Setting Input Selection 2 from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 281:
Configuration Dialog Screen
2.
From the "Inputs and Switch/Input Selection 2" section of the dialog screen select
either "Non-sequential" or "SCADA Cutout".
3.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
355
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......