Figure 285:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 286:
Setpoints Successfully Written To The Control Dialog Screen
6.2.6
Auto/Manual switch type
The Auto/Manual Switch Type setting allows the Auto/Man Switch type on the adapter
panel to be set to "Toggle, SCAMP or None". None is used when no Auto/Manual Switch
exists. The default configuration setting is None.
When the Auto/Manual Switch Type configuration is set to "SCAMP",
the Programmable Alarm Function can be set to function as "Normal" or
"As a Deadman Output". This option is available when SCAMP mode is
used since the Deadman Output is not available.
6.2.6.1
Setting Auto/Man Switch Type from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Section 6
1VAC388793-MB A
Configuration
358
TCC300
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......