GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 294:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 295:
Setpoints Successfully Written To The Control Dialog Screen
6.2.9
Correction factors
6.2.9.1
VT ratio correction
The operation of some regulators is such that the internal VT does not provide the desired
voltage ratio. In these cases, it is desirable to correct the VT secondary voltage to a 120
Vac reference base. This change is easily made in software, eliminating the need for a
multi-tap sensing transformer.
The correction is derived from information provided by the regulator original equipment
manufacturer (OEM). The numerical value of the correction is the value, in volts, required
to adjust the VT nominal secondary voltage to 120.0 volts. The correction range is ±15
volts in 0.1 volt increments.
The maximum allowable continuous VT secondary voltage is 140 volts.
The correction is made only in software. As a result, the value of VLoad
read on the control display will differ from that measured at the voltmeter
test terminals by the percent of the correction voltage.
1VAC388793-MB A
Section 6
Configuration
TCC300
365
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......