Source Side parameters are used when operation mode is regulate reverse
(measured) and the system is in reverse power.
6.2.9.5
Setting CT/Load and/or CT/Source Phase Shift Quantities from the HMI
1.
Press the Down Arrow (CNFG Hot Button) pushbutton to wake the unit. The menu
will advance to "CONFIGURATION".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Nameplate" menu.
The following sequence of steps provide direction for setting the
CT/Load VT Phasing quantities. The steps necessary to set the CT/
Source VT Phasing are similar.
4.
Press the Down arrow pushbutton, as necessary, until the "CT/Load VT Phasing"
screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
CT/Load VT Phasing
0 Deg C
6.
Utilizing the arrow pushbuttons, enter the desired CT/Load VT Phasing value from
0 to 330 Degrees (30 Degree increments), then press the ENT pushbutton.
6.2.9.6
Setting CT/Load and/or CT/Source Phase Shift Quantities from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
369
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......