GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 303:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to the Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 304:
Setpoints Successfully Written To The Control Dialog Screen
6.2.11
Metering factors
The control has the capability of displaying measured and calculated secondary quantities
and calculated primary quantities.
1VAC388793-MB A
Section 6
Configuration
TCC300
373
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......