Cancel press EXIT
10. Press the ENT pushbutton. The following will briefly be displayed confirming the
reset of the counter and then return to the "Reset RTN Succ Ctr" screen.
RTN Succ Ctr Reset
11. Follow the procedure above to enter the desired:
•
Max Allowed Taps
•
Taps Between Runs
•
Max Load Current
•
Max RTN Standby Ops
6.2.17.2
Enabling/Disabling and Setting Run Through Neutral from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 323:
Configuration Dialog Screen
2.
Select "Enable" or "Disable" from the Run Through Neutral section of the dialog
screen.
3.
If Run Through Neutral was "ENABLED", proceed as follows:
4.
Enter the following Run Through Neutral settings:
1VAC388793-MB A
Section 6
Configuration
TCC300
395
User Manual