period the Master does not receive all the GOOSE messages it expected, it will enter
the Master lockout state.
2. Tap Position Response Timeout Lockout – The Tap Position Response Timeout will
start after the Master has published its new tap position message after it has performed
a successful tap operation. If it doesn’t receive the tap position messages from all the
participating Followers in the network before the timer expires, then a Master
Lockout is issued.
3. Tap Difference Lockout – If the Tap position difference between any Follower and
the Master is greater than or equal to Tap Difference setting, the Master will enter the
lockout state.
4. Follower Communication Loss Lockout – If any follower does not send a valid
re
‑
transmitted GOOSE message within a 65 sec internal Follower Detection Lockout
"Keep Alive" time, then a lockout is issued, signaling a broken communication link.
Follower lockout
There are three types of Follower Lockout:
1. Master Communication Loss Lockout – When the Follower does not receive a valid
re-transmitted GOOSE message from the Master within a 65 second internal "Keep
Alive" time, and the previous Master GOOSE message indicates that the breaker
statuses were closed, then a Follower Lockout is activated. This Lockout is an
indication that communication with the Master has been lost.
2. Follower Communication Loss Lockout – If any follower does not send a valid re-
transmitted GOOSE message within a 65 sec internal Keep Alive time, then a lockout
is activated, indicating a broken communication link.
3. Tap Difference Lockout – If the Tap Position Difference between the Follower and
the Master is greater than or equal to the Tap Difference setting, a Follower Lockout
will be activated.
6.3.2.4
Master/follower configuration tool
TCC600® includes a Master/Follower Configuration Tool located in the Utility menu to
help configure the controls for the Master/Follower Paralleling scheme. The tool allows
the user to discover on a Local Area Network (LAN) all the ABB TCC300 controls that
have the Master/Follower feature. Note that the Master/Follower Paralleling scheme can
only be implemented on controls that are on the same network. In addition, if a multiple
network adapter exists on the host computer the configuration tool will allow the user to
select on which network card the tool should perform the discover of all TCC300 controls.
Failure to choose the correct network card may result in the tool not discovering all the
available TCC300 controls. Accessing the Master/Follower Paralleling Tool dialog
screen requires a Level 2 Access code.
1VAC388793-MB A
Section 6
Configuration
TCC300
415
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......