GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 342:
Configuration Dialog Screen
4.
Select "None" from the "Master/Follower Configuration" section of the
"Configuration" dialog screen.
The Master/Follower Configuration settings can also be set utilizing
the Master/Follower Configuration Tool.
GUID-1C232DA5-F848-4026-9280-69A574588EA4 V1 EN
Figure 343:
Master/Follower Configuration Tool Dialog Screen
5.
Enter the desired Master/Follower Configuration Settings from the "Master/
Follower Configuration Settings" section of the "Configuration" dialog screen:
•
Paralleling Address (1 to 16) – The Master Paralleling Address must be the
highest address in the network. All Follower addresses must be a value less
than the Master. The control’ s position in the paralleling network is
determined by its paralleling address. As shown in
, Position 1
Section 6
1VAC388793-MB A
Configuration
418
TCC300
User Manual