Right Tie Breaker Polarity "Positive" or "Negative"
•
Left Tie Breaker "Not In Use" or "In Use" (Auxiliary Input A3)
•
Left Tie Breaker Polarity "Positive" or "Negative"
6.
Drive the Follower Tap Position to match the Master Tap Position.
7.
Repeat Steps 3 through 6 for each Follower in the Master/Follower scheme.
8.
Determine the Master Band Status, then proceed as follows:
9.
If the Master Band Status is "In
‑
Band":
9.1. Select "Master" from the Master, "Master/Follower Configuration" section of
the "Configuration" dialog screen.
After placing the Master control in "Master" the Master will
not respond to any tapchange requests for 32 seconds.
9.2. When at least 32 seconds have elapsed, initiate a Raise or Lower tapchange
from the Master, Remote Control dialog screen "Tap Control" section.
9.3. Verify that all Followers initiate tapchanges to match the Master tap position.
9.4. If necessary, return the Master to an "In-Band" tap position.
9.5. Select "Unblock" from the Master, Remote Control dialog screen "Remote
Operation/Block Auto Control via Communication (Comm Block)" section.
GUID-53E63F94-8E89-48E6-8C7D-3CB55622B3C2 V1 EN
Figure 345:
Remote Control Dialog Screen
10. If the Master Band Status is not In
‑
Band:
1VAC388793-MB A
Section 6
Configuration
TCC300
421
User Manual
Summary of Contents for TCC300
Page 1: ...Digital Tapchanger Control TCC300 User Manual ...
Page 2: ......
Page 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Page 26: ...20 ...
Page 34: ...28 ...
Page 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Page 126: ...120 ...
Page 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Page 260: ...254 ...
Page 328: ...322 ...
Page 494: ...488 ...
Page 556: ...550 ...
Page 580: ...574 ...
Page 600: ...594 ...
Page 700: ...694 ...
Page 710: ...704 ...
Page 712: ...706 ...
Page 713: ...707 ...
Page 714: ......
Page 715: ......